Liebert Comprehensive Specifications for the XDP Network Card

Page 39

Specifications

8.0SPECIFICATIONS

Table 17 Liebert XDP160 specifications

Models

XDP160RC--1

 

XDP160RA--1

 

XDP160RM--1

 

 

 

 

 

 

160kW / 46 Tons, 60Hz

 

140kW / 40 Tons, 50Hz

 

 

 

Cooling Capacity, Nominal

Each capacity is based on 45ºF (7ºC) entering water temperature and

 

140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures

 

 

are used in place of 100% water.

 

The Liebert XDP’s minimum recommended operating load is 20% of system

Minimum Load

nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum

load would be 32 kW. Loading below this value can unfavorably affect system

 

 

operation. Consult factory for any loading below this recommendation.

 

 

 

 

 

 

Electrical Requirements

 

 

 

 

 

 

 

 

 

 

 

Input

208V/3ph/60Hz

 

460V/3/ph60Hz

 

380/415V/3ph/50Hz

 

 

 

 

 

 

Full Load Amps

4A

 

2.1A

 

2.3A

 

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

 

 

 

 

 

Height – Unit only

 

78 (1981)

 

 

 

 

 

 

 

Height – As shipped

 

83 (2108)

 

 

 

 

 

 

 

Width

 

38 (965)

 

 

 

 

 

 

 

Depth

 

34 (864)

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

 

 

 

 

 

Unit only

 

821 (372)

 

 

 

 

Shipping weight

Domestic: 990 (449); Export: 1067 (484)

 

 

 

 

 

 

Installed, with refrigerant and

 

1038 (471)

 

 

chilled water

 

 

 

 

 

 

 

 

Pipe Connections

 

 

 

 

 

 

 

 

 

 

 

Refrigerant supply to Liebert XD

 

 

1-1/8" OD, Cu

 

cooling module

 

 

 

 

 

 

 

 

Refrigerant return from Liebert XD

 

 

2-1/8" OD, Cu

 

cooling module

 

 

 

 

 

 

 

 

Chilled water supply and return

 

 

2-5/8" OD, Cu

 

 

 

Control Valve

2-way, 2" nominal; 35 PSIG close off pressure rating;

 

150 PSIG maximum allowable pressure

 

 

Pressure Drop – Chilled Water

20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate,

Side

 

 

control valve fully open

 

Temperature Rise – Chilled

 

8.0 (4.4)

 

6.9 (3.8)

Water Side at rated flow, °F (°C)

 

 

 

 

 

 

 

Number of Liebert XD cooling units connected, maximum (minimum)

 

Liebert XDCF10

 

16 (4)

 

 

 

 

 

 

 

Liebert XDH20

 

8 (2)

 

 

 

 

 

 

 

Liebert XDH32

 

5 (1)

 

 

 

 

 

 

 

Liebert XDV8

 

20 (4)

 

 

 

 

 

 

 

Liebert XDV10

 

16 (4)

 

 

 

 

 

 

 

Liebert XDO16

 

10 (2)

 

 

 

 

 

 

 

Liebert XDO20

 

8 (2)

 

 

 

 

Cabinet Exterior Finish

Black, matte finish, heat-fused powder coat

 

 

 

 

 

 

Operating Ambient

 

86 (30)

 

 

Temperature, Maximum, °F (°C)

 

 

 

 

 

 

 

 

Agency

 

 

 

 

 

Approvals

CSA 60Hz

 

CE 50Hz

 

 

 

 

 

 

33

Image 39
Contents Liebert XDP Pumping Place holder Revision Unit Redundancy Level Liebert General Safety GuidelinesExample XDP160A Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Specifications Alarm Descriptions and SolutionsFigures Page Product/System Description General Product InformationEquipment Inspection Product DescriptionEquipment Handling Handling With SkidRemoval from Skid Liebert XDP strapped to piano jack Removing pallet boards for piano jack insertionSlide this runner away From the Liebert XDP Removing Piano JacksLiebert XDP dimensions Mechanical ConsiderationsPositioning the Liebert XDP Model Pipe Connection Point 50/60 Hz Unit piping outlet connection sizes, inches, OD CuElectrical Information High Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring High voltage connections-50Hz Extra Low Voltage ELV ConnectionsField Connections-Optional for All Units Field Connections-All UnitsRecommended Pipe Size European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes PipingBypass flow controllers for a Liebert XDP-based system Piping Installation MethodLiebert XDP Interconnection with Liebert XD Cooling Modules Bypass Flow ControllerBypass flow controller arrangement Bypass flow controller details, dimensionsEvacuation and Leak Check Piping Installation MethodPiping Details-Shut-Off/Isolation Valves Piping MainsChecklist for Proper Installation Checklist for Liebert XDP Startup Liebert XDP pump light indicator-208V and 400V unitsIndicator Lights Description Green Red System R-134a liquid level Filling the Pumped Circuit-R-134aSystem refrigerant charge for the supply and return mains Return Line Diameter 5/8Return Line Diameter Total 293 Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Worksheet to calculate refrigerant chargeUser interface keypad functions Feature OverviewMicroprocessor Control DisplayMain Menu Feature OverviewViewing or Changing Settings ControlsMIN Temp SP Active AlarmsAlarm History SetpointsPump Start TD Setup OperationRestart Time Delay DegreesLead Pump Liebert XDP DIP switches and factory settingsPump Wait TD Pump OFF TDPassword Security-SETPT Password and Service Password Change Password-SETPT PasswordValve Time COM Alarm Enable Change Password-SERVICE PasswordAlarm Enable Alarm Time DelayCustom Alarms DiagnosticsCustom Text Alarm Descriptions and Solutions Alarm DescriptionsRed and Green Lamp Indicators Alter Alarm SettingsEnable or Disable Alarms System Shutdown Causes Troubleshooting the XDP TroubleshootingFluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications SpecificationsThat Ne tIti Ti n