Checklist for Liebert XDP Startup
3.0CHECKLIST FOR LIEBERT XDP STARTUP
! CAUTION
Risk of piping and component rupture. May cause injury or equipment damage.
Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves.
NOTE
Before any action that could cause a disturbance in the Liebert XD system’s cooling function is begun, the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed
1.Verify that bypass flow controllers were installed (if applicable), see Table 4.
2.Check all isolation ball valves in the Liebert XDP and Liebert XD cooling module and verify that all are open.
3.Check rotation of the Liebert XDP’s pumps.
On 460V units only, use the rotation device
On 208V units only, view the LED indicator on the
Table 5 | Liebert XDP pump light | ||
|
|
| |
Indicator Lights | Description | ||
|
| ||
Green | Red | ||
| |||
|
|
| |
Off | Off | The electricity supply has been switched off or the pump has been cut out by the thermal switch. | |
|
|
| |
On | Off | The electricity supply has been switched on. Normal operation. | |
|
|
| |
On | On | The electricity supply has been switched on. The direction of rotation is wrong. | |
|
|
|
4.Check rotation of fans on Liebert XD cooling module units.
5.Verify that air is being discharged into the cold aisle.
6.Confirm that the total calculated refrigerant
7.Confirm that the remote temperature/humidity sensor provided has been installed in the correct location.
The correct location is near the return side of a main air mover, such as a Liebert Deluxe System/3. If more than one Liebert XDP is installed, use a different location for each remote sen- sor for best temperature/humidity calculation.
The Liebert XDP system is now ready to be turned ON.
1.Turn On all of the Liebert XD cooling module fans.
2.Turn the Liebert XDP On via its user interface (I/O button). Allow the system to attempt to start for at least 2 minutes.
If the Liebert XDP pump cannot maintain flow and continues to switch over due to starting diffi- culties, proceed to Step 4 and refer to 6.0 - Troubleshooting.
3.If constant flow is established, wait until the Liebert XDP has been operating for
4.Check pressure differential functionality:
The Liebert XDP system should be On. If it is Off:
a.Turn On the Liebert XD cooling module fans
b.Turn the Liebert XDP On via user interface (I/O button).
16