Alarm Descriptions and Solutions
•REFRIG SENS
•LOSS OF
5.2Red and Green Lamp Indicators
•The Green lamp will be on only when The Liebert XDP is On and running with no alarms.
•The Red lamp will be on if the unit is On and running with an active alarm, or if the unit is shut down because of a certain alarm.
•The Red lamp will flash when an alarm is being annunciated. The Red lamp will stop flashing and the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
5.3Alter Alarm Settings
5.3.1Enable or Disable Alarms
At the user’s discretion, some alarms may be enabled or disabled. If an alarm is disabled, the alarm condition will not be monitored and will not trip, will not be in ACTIVE ALARMS, will not be in ALARM HISTORY and will not be annunciated.
These alarms may be enabled or disabled:
•LOSS OF FLOW
•LOSS OF FLOW
•VALVE
•
•HI RMT
•LO RMT
•HI LCL
•LO LCL
To determine whether an alarm is enabled or disabled:
1.Press the MENU key.
2.Use the Up and Down arrow keys to move to the ALARM ENABLE menu.
3.Press the ENTER key to access the menu. Use the Up and Down arrow keys to move through the menu and view which alarms are enabled or disabled. (“YES” means that the alarm is enabled, “NO” means that the alarm is disabled.)
To change an alarm from enabled to disabled, or vice versa
1.Determine whether the alarm is enabled or disabled (see above).
2.Use the Up and Down arrow keys to scroll to the alarm to be changed.
3.Press the ENTER key. (The control will ask for a service password if passwords are enabled. Use the Up and Down arrow keys and ENTER key to enter the
4.Press the ENTER key again to change the alarm.
5.Press the ESC key two to three times to return to the main display.
29