Liebert Series 600T manual Shutdown Procedures System Shutdown Procedure

Page 105

3.3.3Shutdown Procedures

System Shutdown Procedure

Perform a System Shutdown Procedure when you want to remove power from the UPS system and System Con- trol Cabinet (SCC) when required for maintenance, or if you need to perform maintenance on a UPS module in a non-redundant system.

Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in 4.0 - Maintenance.

Use the SCC Monitor/Mimic Display to determine the operating condition of the UPS system. From the SCC Master Menu, select the Shutdown Procedures screen.

Figure 62 SCC Shutdown Procedures Screen

SHUTDOWN PROCEDURES

1.If load is not already being supplied by the bypass line, select the

"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer the load to bypass.

2.Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."

3.Press the ALARM RESET button to clear alarms which are no longer active.

4.If necessary for maintenance purposes, open the static switch disconnect circuit breakers.

5.Wait approximately two (2) minutes before attempting any other action .

Step 1. If the UPS system is supplying power to the load (Load On UPS), select the Load Transfer Procedures screen at the SCC and perform a manual transfer to the bypass line (Load On Bypass). This will open the motor- ized UPS Output circuit breaker (see Figure 9) and close the motorized System Bypass circuit breaker (SBB, Figure 9).

Step 2. If maintenance is required on the Static Bypass Switch, set the Static Switch Disconnects to OFF (open). Refer to Figure 9.

NOTE

Depending on SCC model, the static switch disconnects can be two circuit breakers, contactors, or plug-in connections on a drawout carriage assembly. The location could be at the front, right, or rear of the cabinet. Refer to the drawing of the SCC cabinet selected for your UPS system.

CAUTION

The UPS bypass line is still energized.

Operation 99

DISCONTINUED

PRODUCT

Image 105
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsReliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantControls Hardware Detailed Component DescriptionsFirmware Rectifier/ChargerBattery Charging Circuit Input Power FactorInput Circuit Breaker Isolation TransformerBattery Charge Current Limiting Battery DisconnectBattery Equalize Charge Circuit Operation After End-of-DischargeUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch IsolationFuse Protection Shorted SCR MonitoringLoad Transfers Pulsed Parallel OperationAutomatic Transfers to Bypass Transfer and Retransfer ConditionsManual Transfers Transfer InhibitedRedundant Mode Manual RetransfersRetransfer Inhibited Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenLoad Transfer Procedures SCC only Battery Time modules onlyCustomer Alarm Definitions SCC only Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery CB Open DC Ground FaultPower BatteryStatic Switch Manual ResetBypass Phase Control PowerIndications and Other Alarms That Activate Summary Alarms AlarmSystem Configuration Screens or the watchdog timer has Reverse PowerOver-Temperature TemperatureTimeout System Configuration Screens Load On UPSSpecial Functions Alarm MessageWorldwide Reporting Communication InterfacesAuto-Dial Requesting InformationLocal Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass System BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Power Batteries Matching Battery Cabinets OptionalRack-Mounted Batteries Torque RequirementsDetection of Trouble Torque Specifications Unless Otherwise LabeledReporting a Problem Corrective ActionsRecommended Test Equipment Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Phase Balancing Voltage Adjustment RangeVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS