3.2.10Maintenance Bypass
Maintenance Bypass switchgear (cabinet, panelboard, switchboard or custom switchgear) allows you to totally isolate the UPS system from all power sources, while you maintain power to the critical load.
Your installation may have a
Another option that may be present at your site is an alternate power source (generator) and an automatic transfer switch (ATS).
Note that to totally isolate the UPS system from all power sources, the Main Input switchgear and battery circuit breakers must also be opened.
CAUTION
Instructions for operating the Maintenance Bypass circuit breakers are on the Maintenance Bypass cabinet. Make sure you understand the proper sequence before operating any circuit breaker. Operating a Maintenance Bypass circuit breaker out of sequence could cut off power to the critical load.
Figure 57 Load on Maintenance Bypass (Two Breakers)
|
|
|
| RIB |
|
|
|
| RIB |
|
|
| RIB |
|
|
|
| BIB | BFB |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UPS #3 | UPS #2 | UPS | #1 |
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CB1 |
|
| CB1 |
|
| CB1 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| SBS |
|
|
|
|
|
|
|
|
|
|
|
|
| R |
|
| R |
|
| R |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| SBB |
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| MBB | |||
|
| I |
|
| I |
|
| I |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| System |
|
|
|
|
|
|
|
|
|
| |
CB2 |
|
|
| CB2 |
|
|
| CB2 |
|
|
|
|
|
| SKRU | |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
| Controls |
|
|
|
|
|
|
|
|
|
|
Output MIB
|
|
|
|
|
|
|
|
| SCCT | |
|
|
|
|
|
|
|
|
| To Critical Load | |
|
|
|
|
|
|
|
|
| ||
|
| MBD |
|
| MBD |
|
|
| MBD | |
|
|
|
|
|
|
|
|
| SCCT | |
Battery | Battery | Battery | ||||||||
(can accommodate up to 6 UPS modules) | ||||||||||
|
|
|
|
|
|
|
|
|
88 | Operation | DISCONTINUED |
|