Maximum Auto-Retransfer Attempts
When a UPS output overload condition exceeds a
If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload condition.
Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will not be initiated. Refer to 3.4.3 - Automatic Retransfers to UPS.
Figure 34 Maximum Auto-Retransfer Attempts Screen
MAX
LOWER INPUT
0
UP : INCREASE
DOWN : DECREASE
SELECT : EXIT
VALUE
3
UPPER LIMIT
5
To change the Maximum
1.From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto-
Retransfer Attempts.
2.Press the Select pad. The screen above will appear.
3.Press the Up pad to increase the value or the Down pad to decrease it.
4.Press the Select pad to set the value and to return to the System Configuration screen.
Operation 53