Maximum Auto-Retransfer Attempts

When a UPS output overload condition exceeds a pre-programmed current-versus-time window (based on the SCC current rating), the UPS automatically transfers the critical load to the bypass line. After the overload condi- tion has been corrected, the UPS attempts to automatically retransfer the critical load to the UPS output (unless zero attempts is selected). The Maximum Auto-Retransfer Attempts limits the number of times (0 to 5) that the UPS attempts to retransfer the load back to the UPS within a one-hour time period.

If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload condition.

Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will not be initiated. Refer to 3.4.3 - Automatic Retransfers to UPS.

Figure 34 Maximum Auto-Retransfer Attempts Screen

MAX AUTO-REXFER ATTEMPTS

LOWER INPUT

0

UP : INCREASE

DOWN : DECREASE

SELECT : EXIT

VALUE

3

UPPER LIMIT

5

To change the Maximum Auto-Retransfer Attempts parameter, do the following at the SCC:

1.From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto-

Retransfer Attempts.

2.Press the Select pad. The screen above will appear.

3.Press the Up pad to increase the value or the Down pad to decrease it.

4.Press the Select pad to set the value and to return to the System Configuration screen.

Operation 53

DISCONTINUED

PRODUCT

Image 59
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsOther Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantRectifier/Charger Detailed Component DescriptionsControls Hardware FirmwareIsolation Transformer Input Power FactorBattery Charging Circuit Input Circuit BreakerOperation After End-of-Discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterShorted SCR Monitoring Static Switch IsolationStatic Bypass Fuse ProtectionLoad Transfers Pulsed Parallel OperationTransfer Inhibited Transfer and Retransfer ConditionsAutomatic Transfers to Bypass Manual TransfersRetransfer Inhibited Redundant ModeManual Retransfers Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenCustomer Alarm Definitions SCC only Load Transfer Procedures SCC onlyBattery Time modules only Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 6 System Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 5 Module Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery DC Ground FaultBattery CB Open PowerControl Power Manual ResetStatic Switch Bypass PhaseReverse Power AlarmIndications and Other Alarms That Activate Summary Alarms System Configuration Screens or the watchdog timer hasSystem Configuration Screens Load On UPS TemperatureOver-Temperature TimeoutSpecial Functions Alarm MessageRequesting Information Communication InterfacesWorldwide Reporting Auto-DialRemote Monitor Panel Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures System Bypass Maintenance Bypass Load TransfersMaintenance Bypass If the load is on Maintenance BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpAir Filters Routine MaintenanceRecord Log Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Torque Requirements Matching Battery Cabinets OptionalPower Batteries Rack-Mounted BatteriesDetection of Trouble Torque Specifications Unless Otherwise LabeledRecommended Test Equipment Reporting a ProblemCorrective Actions Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Voltage Harmonic Content Voltage Adjustment RangePhase Balancing Voltage Transient Recovery TimeSeries 600T UPS