Liebert Series 600T manual Emergency Off, Ambient Over, Temperature, Blower Failed, Equipment Over

Page 79

Table 1

 

Alarm Messages - Meaning and Corrective Action (continued)

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

UPS SYSTEM (Contʼd.)

 

 

Hardware

 

MMU

D#

At least one of the following alarm conditions is present: Inverter

Shutdown

 

 

 

Fault, Rectifier Fuse Blown, Reverse Power, Overload Shutdown,

 

 

 

 

logic power supply failure, or inverter output symmetry failure. The

 

 

 

 

UPS module is taken off-line and is shut down.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset the

 

 

 

 

circuit breakers.]

Emergency Off

 

SCC

D*, L, S

The Emergency Module Off (or Emergency Power Off) switch has

 

 

MMU

 

been pressed, which caused the UPS system to shut down and

 

 

 

 

transfer the load to the bypass line (or all power to the critical load

 

 

 

 

has been shutdown).

 

 

 

 

[Determine the cause of the emergency condition and correct it if

 

 

 

 

possible. Contact Liebert Global Services if you require assistance.]

COOLING

 

 

 

 

Ambient Over-

 

MMU

R, S

The intake air to the UPS module exceeds the specified maximum

Temperature

 

 

 

temperature.

 

 

 

 

[This condition only causes an alarm, but should be corrected

 

 

 

 

immediately to prevent damage to equipment due to overheating.]

Blower Failed

 

MMU

S

A fault in one or more of the blower motors has occurred. This

 

 

 

 

condition only causes an alarm, but if not promptly corrected it could

 

 

 

 

cause an equipment over-temperature condition that would shut

 

 

 

 

down the UPS module.

 

 

 

 

[Check the blowers for proper operation. Contact Liebert Global

 

 

 

 

Services if you require assistance.]

Equipment Over-

 

MMU

S

Sensors on power semiconductor heatsinks detect temperatures

Temperature

 

 

 

above the steady state limits for these components. The control logic

 

 

 

 

sets off the alarm but does not shut down the UPS module if the

 

 

 

 

condition lasts less than 10 minutes.

 

 

 

 

[Check the air intake, air exhaust, and filters. Reduce the load or

 

 

 

 

transfer it to bypass. Contact Liebert Global Services if the alarm

 

 

 

 

persists.]

Over-Temperature

MMU

D, F

An Equipment Over-Temperature condition has persisted for more

Timeout

 

 

 

than 10 minutes. The UPS module is taken off-line and is shut down.

 

 

 

 

[Check the air intake, air exhaust, and filters before attempting to

 

 

 

 

start-up the UPS.]

REMOTE MONITOR

PANELS

 

 

(Refer also to SCC and Module Remote Monitor Indications and Other Alarms That Activate Summary Alarms in

3.1.5 - System Configuration Screens)

 

Load On UPS

 

R (SCC)

The UPS is operating properly. No corrective action is necessary.

New Alarm

 

R (SCC)

Another new alarm message has been registered on the UPS

 

 

 

R (MMU)

system.

 

 

 

 

[Clear the new alarm condition, if possible.]

System Summary

R (SCC)

One or more of the UPS system alarm messages has been activated

Alarm

 

 

 

or a control logic failure has been detected by a watchdog timer.

 

 

 

 

[Use the Present Status screen to determine which alarms are

 

 

 

 

active. Clear the new alarm condition if possible to do so.]

Module Summary

R (MMU)

One or more of the UPS module alarm messages has been

Alarm

 

 

 

activated.

 

 

 

 

[Use the Present Status screen to determine which alarms are

 

 

 

 

active. Clear the new alarm condition, if possible to do so.]

Table 1 Abbreviations

 

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

Operation 73

DISCONTINUED

PRODUCT

Image 79
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsDesigned for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantRectifier/Charger Detailed Component DescriptionsControls Hardware FirmwareIsolation Transformer Input Power FactorBattery Charging Circuit Input Circuit BreakerOperation After End-of-Discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterShorted SCR Monitoring Static Switch IsolationStatic Bypass Fuse ProtectionLoad Transfers Pulsed Parallel OperationTransfer Inhibited Transfer and Retransfer ConditionsAutomatic Transfers to Bypass Manual TransfersManual Retransfers Redundant ModeRetransfer Inhibited Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenBattery Time modules only Load Transfer Procedures SCC onlyCustomer Alarm Definitions SCC only Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 6 System Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 5 Module Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery DC Ground FaultBattery CB Open PowerControl Power Manual ResetStatic Switch Bypass PhaseReverse Power AlarmIndications and Other Alarms That Activate Summary Alarms System Configuration Screens or the watchdog timer hasSystem Configuration Screens Load On UPS TemperatureOver-Temperature TimeoutSpecial Functions Alarm MessageRequesting Information Communication InterfacesWorldwide Reporting Auto-DialRemote Monitor Panel Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures System Bypass Maintenance Bypass Load TransfersMaintenance Bypass If the load is on Maintenance BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpRecord Log Routine MaintenanceAir Filters Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Torque Requirements Matching Battery Cabinets OptionalPower Batteries Rack-Mounted BatteriesDetection of Trouble Torque Specifications Unless Otherwise LabeledCorrective Actions Reporting a ProblemRecommended Test Equipment Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Voltage Harmonic Content Voltage Adjustment RangePhase Balancing Voltage Transient Recovery TimeSeries 600T UPS
Related manuals
Manual 84 pages 39.26 Kb