Liebert Series 600T manual Module Shutdown Procedures Screen

Page 67

Go to the module Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad and the module Shutdown Procedures screen is displayed.

This two-page screen contains the steps you must follow to perform a controlled shutdown of each UPS module. The instructions are listed so you can review them before performing the controlled shutdown.

Figure 40 Module Shutdown Procedures Screen

DOWN : NEXT PAGE

SELECT : MASTER MENU

SHUTDOWN PROCEDURES

1.If load can not be supported by the remaining modules when this module is taken off line, go to the system control cabinet and select the "LOAD TRANSFER PROCEDURES" screen. Follow the instructions to transfer to bypass.

2.Open the module output breaker by simultaneously pressing the OUTPUT TRIP and CONTROL ENABLE pushbuttons.

3.Open the module battery breaker by simultaneously pressing the BATTERY TRIP and CONTROL ENABLE pushbuttons.

4.Manually open the input breaker by moving the handle to the OFF position.

UP : FIRST PAGE

SELECT : MASTER MENU

SHUTDOWN PROCEDURES (Cont'd)

5.Verify breaker status on the "MONITOR / MIMIC" screen.

6.If necessary for maintenance purposes, turn the control power switch (fuse disconnect on some models) to the OFF position.

7.Wait a minimum of two (2) minutes before attempting any other action.

To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line (at the SCC). Then trip open the UPS module output and battery circuit breaker (MBD), and manually open the UPS module input circuit breaker. The Control Power switch may be turned Off if required for maintenance proce- dures.

Refer to 3.3.3 - Shutdown Procedures for more details, including module shutdowns for service and emergency shutdowns.

Operation 61

DISCONTINUED

PRODUCT

Image 67
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsDesigned for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantRectifier/Charger Detailed Component DescriptionsControls Hardware FirmwareIsolation Transformer Input Power FactorBattery Charging Circuit Input Circuit BreakerOperation After End-of-Discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterShorted SCR Monitoring Static Switch IsolationStatic Bypass Fuse ProtectionLoad Transfers Pulsed Parallel OperationTransfer Inhibited Transfer and Retransfer ConditionsAutomatic Transfers to Bypass Manual TransfersManual Retransfers Redundant ModeRetransfer Inhibited Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenBattery Time modules only Load Transfer Procedures SCC onlyCustomer Alarm Definitions SCC only Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Item 6 System Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 5 Module Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery DC Ground FaultBattery CB Open PowerControl Power Manual ResetStatic Switch Bypass PhaseReverse Power AlarmIndications and Other Alarms That Activate Summary Alarms System Configuration Screens or the watchdog timer hasSystem Configuration Screens Load On UPS TemperatureOver-Temperature TimeoutSpecial Functions Alarm MessageRequesting Information Communication InterfacesWorldwide Reporting Auto-DialRemote Monitor Panel Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures System Bypass Maintenance Bypass Load TransfersMaintenance Bypass If the load is on Maintenance BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpRecord Log Routine MaintenanceAir Filters Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Torque Requirements Matching Battery Cabinets OptionalPower Batteries Rack-Mounted BatteriesDetection of Trouble Torque Specifications Unless Otherwise LabeledCorrective Actions Reporting a ProblemRecommended Test Equipment Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Voltage Harmonic Content Voltage Adjustment RangePhase Balancing Voltage Transient Recovery TimeSeries 600T UPS