The Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con- trol logic at the System Control Cabinet (SCC) monitors the performance of the UPS system, the availability of power sources, and the current required by the critical load.
The system control logic at the SCC:
1.Determines what overload conditions can be sustained without a transfer to bypass.
2.Initiates an automatic transfer to bypass to sustain an overload.
3.Can initiate an automatic retransfer to the UPS after a system overload has been cleared.
4.Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS fault occurs.
The control logic at each UPS module:
1.Determines what overload conditions can be sustained by the module while it is
2.Automatically takes the UPS module off line and initiates an emergency module shutdown when selected UPS faults occur.
Refer to 3.4 - Automatic Operations for more details.
Manual procedures available to the operator include
The LCD display at each UPS cabinet includes a screen to help you with each manual procedure by listing each step you must perform.
This section lists
1.
2.Load Transfers: including transfers from UPS system to bypass, and retransfers from bypass to the UPS system.
3.Shutdowns: including module shutdowns for maintenance procedures and emergency shutdowns.