Liebert Series 600T manual Momentary Overloads, Refer to 3.4 Automatic Operations

Page 87

3.2.3Momentary Overloads

An overload in the critical load will continue to be supplied by the UPS system if the overload condition does not exceed the current versus time curve of overload capacity for either the SCC rating or for the number of modules on-line.

For momentary overloads exceeding 155% of rated system (SCC) current, the static switch turns on for 40 milli- seconds to provide current from the bypass line in parallel with current from the UPS system output. Up to 1000% of rated current can be supplied for less than one cycle, while up to 500% of rated load can be sustained for the full 40 milliseconds of pulsed-parallel operation. By providing two power sources simultaneously, high current can be supplied to the critical load with full output voltage regulation. The critical load can be supported through inrush currents and momentary faults without operating the motorized circuit breakers.

If an overload situation exceeds 40 milliseconds, the UPS system continues to supply power to the critical load if it remains within the current versus time curve of overload capacity. If the system overload capacity is exceeded, the UPS control logic at the SCC initiates an automatic transfer to the bypass line by operating the static bypass switch and the motorized system circuit breakers (SBB and UPS Output).

Refer to 3.4 - Automatic Operations.

Figure 50 Momentary Overload (Pulsed Static Bypass Switch)

 

 

 

RIB

 

 

 

 

RIB

 

 

RIB

 

 

 

 

BFB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS #3

UPS #2

UPS

#1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB1

 

 

CB1

 

 

CB1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

R

 

R

 

 

 

 

 

BIB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SBB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

I

 

I

 

 

 

 

 

 

 

 

 

 

 

MBB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB2

 

 

CB2

 

 

 

CB2

 

System

 

 

 

 

SKRU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

Output MIB

 

 

 

 

 

 

 

 

 

SCCT

 

 

MBD

 

 

 

 

 

 

To Critical Load

 

 

 

 

 

 

 

 

 

 

 

 

MBD

 

 

 

MBD

Battery

 

 

 

 

 

 

SCCT

Battery

Battery

(can accommodate up to 6 UPS modules)

 

 

 

 

 

 

 

 

 

Operation 81

DISCONTINUED

PRODUCT

Image 87
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsReliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantRectifier/Charger Detailed Component DescriptionsControls Hardware FirmwareIsolation Transformer Input Power FactorBattery Charging Circuit Input Circuit BreakerOperation After End-of-Discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterShorted SCR Monitoring Static Switch IsolationStatic Bypass Fuse ProtectionLoad Transfers Pulsed Parallel OperationTransfer Inhibited Transfer and Retransfer ConditionsAutomatic Transfers to Bypass Manual TransfersRedundant Mode Manual RetransfersRetransfer Inhibited Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenLoad Transfer Procedures SCC only Battery Time modules onlyCustomer Alarm Definitions SCC only Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 6 System Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 5 Module Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery DC Ground FaultBattery CB Open PowerControl Power Manual ResetStatic Switch Bypass PhaseReverse Power AlarmIndications and Other Alarms That Activate Summary Alarms System Configuration Screens or the watchdog timer hasSystem Configuration Screens Load On UPS TemperatureOver-Temperature TimeoutSpecial Functions Alarm MessageRequesting Information Communication InterfacesWorldwide Reporting Auto-DialRemote Monitor Panel Local Reporting to a TerminalLocal Reporting to a Monitor Site Reporting SiteScan or SnmpSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures System Bypass Maintenance Bypass Load TransfersMaintenance Bypass If the load is on Maintenance BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpRoutine Maintenance Record LogAir Filters Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Torque Requirements Matching Battery Cabinets OptionalPower Batteries Rack-Mounted BatteriesDetection of Trouble Torque Specifications Unless Otherwise LabeledReporting a Problem Corrective ActionsRecommended Test Equipment Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Voltage Harmonic Content Voltage Adjustment RangePhase Balancing Voltage Transient Recovery TimeSeries 600T UPS