Liebert Series 600T Input Fail, DC Ground Fault, DC Capacitor, Fuse Blown, Battery CB Open, Power

Page 76

Table 1

 

Alarm Messages - Meaning and Corrective Action

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

AC INPUT

 

 

 

 

Input Fail

 

MMU

The rectifier input line voltage is outside of specified limits or the

 

 

 

 

input circuit breaker is opened while the battery circuit breaker

 

 

 

 

remains closed. The battery supplies power to the critical load

 

 

 

 

through the UPS inverter.

DC BUS

 

 

 

 

DC Ground Fault

 

MMU

L, S

Either the positive (+) or negative (-) DC bus is grounded. No transfer

 

 

 

 

or shutdown occurs.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to locate or

 

 

 

 

repair the fault.]

DC Capacitor

 

MMU

D, F, S

At least one DC capacitor fuse has opened. The UPS module is

Fuse Blown

 

 

 

taken off-line and the input and battery circuit breakers trip open.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset the

 

 

 

 

circuit breakers.]

Battery CB Open

 

MMU

R, S

The module battery circuit breaker (MBD) is open. This circuit

 

 

 

 

breaker can be opened either manually or automatically in a UPS

 

 

 

 

shutdown procedure. If the UPS is operating with this breaker open,

 

 

 

 

the critical load is not protected from loss of the utility source

 

 

 

 

power.

 

 

 

 

[After AC power is restored and the DC bus is at 100% operating

 

 

 

 

voltage, manually close the battery circuit breaker so the rectifier can

 

 

 

 

charge the battery.]

Battery

 

MMU

R, S

The battery is discharging. This occurs whenever the battery

Discharging

 

 

 

supplies power to the load for more than 5 seconds because of input

 

 

 

 

power failure, a rectifier problem, or an overload condition. If the

 

 

 

 

input power or a source of auxiliary power is restored to the UPS

 

 

 

 

module, the UPS automatically returns to normal operation.

 

 

 

 

[Watch the battery voltage carefully. Reduce the load (begin

 

 

 

 

controlled shutdown) to extend the battery back-up time. Reset the

 

 

 

 

UPS alarms after the input power is restored. The message clears

 

 

 

 

after 30 seconds.]

Low Battery

 

MMU

R, S

The battery voltage is approaching the minimum discharge voltage

Warning

 

 

 

(approximately 5 minutes remaining).

 

 

 

 

[Complete the controlled shutdown of the critical load. Reset the

 

 

 

 

alarms if the input power is restored before shutdown.]

Low Battery

 

MMU

D, F, L, S

The battery voltage has decreased to the minimum discharge value.

Shutdown

 

 

 

The UPS module is taken off-line (no power to the critical load)

 

 

 

 

and the battery and input circuit breakers trip open.

 

 

 

 

[Perform a UPS system start-up procedure when AC power

 

 

 

 

becomes available.]

DC Over-Voltage

 

MMU

D, F, L, S

The maximum preset value of the DC Bus voltage has been

Shutdown

 

 

 

exceeded. The UPS module is taken off-line and the input and

 

 

 

 

battery circuit breakers trip open.

 

 

 

 

[Contact Liebert Global Services at once. A fault may have occurred

 

 

 

 

within the UPS. Do not attempt to reset the circuit breaker.]

BYPASS

 

 

 

 

Load On Bypass

 

SCC

D, E, F

The critical load is being supplied power from the bypass line, and is

 

 

 

 

therefore exposed to utility power disturbances.

 

 

 

 

[Clear all of the alarms before attempting to retransfer the load from

 

 

 

 

the bypass line to the UPS.]

Table 1 Abbreviations

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

70

Operation

DISCONTINUED

 

 

PRODUCT

Image 76
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual System Description Multi-Module UPS, 65-80 kVA left and 100-500 kVA rightProduct Multi-Module 500-750 kVA UPS Types of System Control Cabinets SCCs System Control Cabinets SCCsDesigned for Success ReliabilityOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options General Component Descriptions System Control CabinetBattery Plant UPS ModuleDetailed Component Descriptions Controls HardwareFirmware Rectifier/ChargerInput Power Factor Battery Charging CircuitInput Circuit Breaker Isolation TransformerBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-DischargeNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Isolation Static BypassFuse Protection Shorted SCR MonitoringPulsed Parallel Operation Load TransfersTransfer and Retransfer Conditions Automatic Transfers to BypassManual Transfers Transfer InhibitedManual Retransfers Redundant ModeRetransfer Inhibited Features Display Screen and Operator ControlsDescription Function System Control Cabinet Operator Controls Sccb Pictured Shutdown Procedures Description Location FunctionSwitches Behind SCC Control Panel Door Menu Tree Master Menu Screen WALK-IN Display modules onlyBattery Time modules only Load Transfer Procedures SCC onlyCustomer Alarm Definitions SCC only Input Metering Displays Monitor/Mimic Display ScreenOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Alarm Messages Item 5 Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen Walk-In Display Screen During Start-UpStatus Reports Screens Status Reports ScreenPresent Status Select ExitEvent History Event History MODULE-0History Status History Status Report ScreensSCC ModuleBattery Cycle Monitor Module Only System StatusBattery Cycle Monitoring Summary Screen System Configuration Screens System ConfigurationDate Date ScreenTime Time ScreenAuto Dial DialModem Baud Rate Modem Baud RateMaximum Auto-Retransfer Attempts Retransfer AttemptsRemote Monitor Alarm Limit Settings Screen Alarm SettingsProduct Load Transfer Procedures Screen Refer to 3.3.2 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.3.1 Start-Up Procedure for more detailsModule Start- Up Procedures Screen Shutdown Procedures Screen Shutdown ProceduresModule Shutdown Procedures Screen Battery Time Screen Module Only VDCBattery Time Screen Example 45 Minute Discharge Range of Values for Calculated Battery Times Aining Rem Tim Calculated La p s e d T im e M in u te sMeter Calibration Screen UP Cursor UP Down Cursor Down Select ChooseBattery Equalize Screen Battery Equalize RechargingAlarm and Status Messages Module Status Messages 3 Modules ConnectedSystem Status Messages Load Block MessagesAbbreviations Used in Alarm Messages OF/UFDC Ground Fault Battery CB OpenPower BatteryManual Reset Static SwitchBypass Phase Control PowerAlarm Indications and Other Alarms That Activate Summary AlarmsSystem Configuration Screens or the watchdog timer has Reverse PowerTemperature Over-TemperatureTimeout System Configuration Screens Load On UPSAlarm Message Special FunctionsCommunication Interfaces Worldwide ReportingAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Load On Bypass ScctOK To Transfer Load on Bypass UPS AvailableLoad on UPS Bypass Available Momentary Overloads Refer to 3.4 Automatic OperationsInput Power Failure Load On Battery Input Power Fail Load on BatteryOne Module Off-Line One Module Off-Line Load on UPSOff Battery Load on UPS Battery Not AvailableRefer to 3.3.3 Shutdown Procedures Emergency Modules OffEmergency Power Off Emergency Power OffRefer to 3.2.10 Maintenance Bypass System ShutdownLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Manual Procedures Refer to 3.4 Automatic Operations for more detailsStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Load Transfers Maintenance BypassIf the load is on Maintenance Bypass System BypassShutdown Procedures System Shutdown Procedure UPS bypass line is still energized100 Module Shutdown Procedure Remote Emergency Power Off Repo Local Emergency Modules Off LemoAutomatic Operations Overloads Without TransferAutomatic Transfers to Bypass Automatic Retransfers to UPSAutomatic Module Off-Line Automatic Emergency Modules OffMaintenance DIS Product Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRecord Log Routine MaintenanceAir Filters Battery Maintenance Battery Safety PrecautionsDIS Product 112 DIS Product Matching Battery Cabinets Optional Power BatteriesRack-Mounted Batteries Torque RequirementsTorque Specifications Unless Otherwise Labeled Detection of TroubleCorrective Actions Reporting a ProblemRecommended Test Equipment Rating Environmental Conditions Adjustments Battery OperationElectrical Specifications Voltage Adjustment Range Phase BalancingVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS
Related manuals
Manual 84 pages 39.26 Kb