Table 1 |
| Alarm Messages - Meaning and Corrective Action | ||
Alarm |
| Cabinet | Special | Meaning and |
Message |
| Location | Functions | Corrective Action in Brackets [ ] |
AC INPUT |
|
|
|
|
Input Fail |
| MMU | — | The rectifier input line voltage is outside of specified limits or the |
|
|
|
| input circuit breaker is opened while the battery circuit breaker |
|
|
|
| remains closed. The battery supplies power to the critical load |
|
|
|
| through the UPS inverter. |
DC BUS |
|
|
|
|
DC Ground Fault |
| MMU | L, S | Either the positive (+) or negative |
|
|
|
| or shutdown occurs. |
|
|
|
| [Contact Liebert Global Services at once. Do not attempt to locate or |
|
|
|
| repair the fault.] |
DC Capacitor |
| MMU | D, F, S | At least one DC capacitor fuse has opened. The UPS module is |
Fuse Blown |
|
|
| taken |
|
|
|
| [Contact Liebert Global Services at once. Do not attempt to reset the |
|
|
|
| circuit breakers.] |
Battery CB Open |
| MMU | R, S | The module battery circuit breaker (MBD) is open. This circuit |
|
|
|
| breaker can be opened either manually or automatically in a UPS |
|
|
|
| shutdown procedure. If the UPS is operating with this breaker open, |
|
|
|
| the critical load is not protected from loss of the utility source |
|
|
|
| power. |
|
|
|
| [After AC power is restored and the DC bus is at 100% operating |
|
|
|
| voltage, manually close the battery circuit breaker so the rectifier can |
|
|
|
| charge the battery.] |
Battery |
| MMU | R, S | The battery is discharging. This occurs whenever the battery |
Discharging |
|
|
| supplies power to the load for more than 5 seconds because of input |
|
|
|
| power failure, a rectifier problem, or an overload condition. If the |
|
|
|
| input power or a source of auxiliary power is restored to the UPS |
|
|
|
| module, the UPS automatically returns to normal operation. |
|
|
|
| [Watch the battery voltage carefully. Reduce the load (begin |
|
|
|
| controlled shutdown) to extend the battery |
|
|
|
| UPS alarms after the input power is restored. The message clears |
|
|
|
| after 30 seconds.] |
Low Battery |
| MMU | R, S | The battery voltage is approaching the minimum discharge voltage |
Warning |
|
|
| (approximately 5 minutes remaining). |
|
|
|
| [Complete the controlled shutdown of the critical load. Reset the |
|
|
|
| alarms if the input power is restored before shutdown.] |
Low Battery |
| MMU | D, F, L, S | The battery voltage has decreased to the minimum discharge value. |
Shutdown |
|
|
| The UPS module is taken |
|
|
|
| and the battery and input circuit breakers trip open. |
|
|
|
| [Perform a UPS system |
|
|
|
| becomes available.] |
DC |
| MMU | D, F, L, S | The maximum preset value of the DC Bus voltage has been |
Shutdown |
|
|
| exceeded. The UPS module is taken |
|
|
|
| battery circuit breakers trip open. |
|
|
|
| [Contact Liebert Global Services at once. A fault may have occurred |
|
|
|
| within the UPS. Do not attempt to reset the circuit breaker.] |
BYPASS |
|
|
|
|
Load On Bypass |
| SCC | D, E, F | The critical load is being supplied power from the bypass line, and is |
|
|
|
| therefore exposed to utility power disturbances. |
|
|
|
| [Clear all of the alarms before attempting to retransfer the load from |
|
|
|
| the bypass line to the UPS.] |
Table 1 Abbreviations |
|
| ||
D = | L = latches |
|
| |
E = reports only; | R = remote |
|
| |
F = freezes; | S = summary |
|
|
D* =
D# =
70 | Operation | DISCONTINUED |
|
| PRODUCT |