Liebert Series 600T Bypass, Auto Retransfer, Primed, Manual Reset, Static Switch, Unable, Fail

Page 77

Table 1

 

Alarm Messages - Meaning and Corrective Action (continued)

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

BYPASS (Contʼd.)

 

 

 

Auto Transfer to

 

SCC

D, E, F

The critical load has been automatically transferred to the bypass

Bypass

 

 

 

line.

 

 

 

 

[Use the History Status screen to determine the cause for the

 

 

 

 

transfer. Clear all of the alarms before attempting to retransfer the

 

 

 

 

load from bypass to UPS.]

Auto Retransfer

 

SCC

An automatic retransfer will be initiated when the OK to Transfer

Primed

 

 

 

condition has been present for 10 seconds, if the overload has

 

 

 

 

dropped below 100% of the rated SCC current and if enough UPS

 

 

 

 

modules are on-line.

Manual Reset/

 

SCC

A manual retransfer is required. Either a system overload condition

Retransfer

 

 

 

has lasted more than 5 minutes, or no more auto-retransfer attempts

 

 

 

 

are available. Note that this alarm is only used if auto-retransfer

 

 

 

 

attempts are enabled.

 

 

 

 

[Perform a manual retransfer if all necessary conditions are present.]

Static Switch

 

SCC

S

The UPS output is not synchronized to the bypass power source.

Unable

 

 

 

The static bypass switch is disconnected, or it has failed internally.

 

 

 

 

[Emergency and overload transfer to the bypass source is not

 

 

 

 

available. Manually set the Static Switch Disconnects to ON (closed)

 

 

 

 

if the static switch is disconnected. If the alarm conditions are

 

 

 

 

automatically corrected, reset the alarm to clear it. Contact Liebert

 

 

 

 

Global Services if the alarm stays on.]

Bypass Not

 

SCC

The bypass power source voltage is not within specifications.

Available

 

 

 

[Check the bypass power source.]

Bypass Phase

 

SCC

The power conductors on the bypass line are not wired to the UPS in

Sequence Wrong

 

 

the required sequence. This alarm should appear only during initial

 

 

 

 

start-up or after a repair to the source power system.

 

 

 

 

[Disconnect power from the bypass line and correct the wiring. A

 

 

 

 

Liebert Global Services representative must be present during initial

 

 

 

 

start-up of your UPS System.]

UPS SYSTEM

 

 

 

 

Input Current

 

MMU

E

At least one input phase differs from the average current by 10% or

Unbalanced

 

 

 

more for four (4) hours. Contact Liebert Global Services. If the

 

 

 

 

condition persists, transfer the load to the bypass line.

Control Power

 

SCC

L, S

The logic control power supply from the UPS output is not operating

Fail

 

MMU

L, R, S

properly. The UPS module continues operating but will shut down if

 

 

 

 

the input power fails. The SCC continues operating but will shut

 

 

 

 

down if the bypass power fails. Contact Liebert Global Services

 

 

 

 

immediately.

Output Over/

 

SCC

L, S

Output frequency differs from the nominal (60 Hz) by more than 0.5

Under Frequency

 

 

Hz. No transfer or shutdown occurs.

 

 

 

 

[Contact Liebert Global Services at once.]

Output Under-

 

SCC

D, F, L, S

The UPS system output voltage is under the minimum (-12%)

Voltage

 

 

 

deviation from nominal. The load automatically transfers to the

 

 

 

 

bypass line.

 

 

 

 

[If the alarm condition is no longer present, reset the alarm and

 

 

 

 

retransfer the load from bypass to UPS. Contact Liebert Global

 

 

 

 

Services if alarm persists.]

Output Over-

 

SCC

D, F, L, S

The UPS system output voltage is above the maximum (+10%)

Voltage

 

 

 

deviation from nominal. The load automatically transfers to the

 

 

 

 

bypass line. All UPS modules are taken off-line and are shut down.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset

 

 

 

 

circuit breakers.]

Table 1 Abbreviations

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

Operation 71

DISCONTINUED

PRODUCT

Image 77
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsOther Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantControls Hardware Detailed Component DescriptionsFirmware Rectifier/ChargerBattery Charging Circuit Input Power FactorInput Circuit Breaker Isolation TransformerBattery Charge Current Limiting Battery DisconnectBattery Equalize Charge Circuit Operation After End-of-DischargeUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch IsolationFuse Protection Shorted SCR MonitoringLoad Transfers Pulsed Parallel OperationAutomatic Transfers to Bypass Transfer and Retransfer ConditionsManual Transfers Transfer InhibitedRetransfer Inhibited Redundant ModeManual Retransfers Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenCustomer Alarm Definitions SCC only Load Transfer Procedures SCC onlyBattery Time modules only Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery CB Open DC Ground FaultPower BatteryStatic Switch Manual ResetBypass Phase Control PowerIndications and Other Alarms That Activate Summary Alarms AlarmSystem Configuration Screens or the watchdog timer has Reverse PowerOver-Temperature TemperatureTimeout System Configuration Screens Load On UPSSpecial Functions Alarm MessageWorldwide Reporting Communication InterfacesAuto-Dial Requesting InformationLocal Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass System BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Power Batteries Matching Battery Cabinets OptionalRack-Mounted Batteries Torque RequirementsDetection of Trouble Torque Specifications Unless Otherwise LabeledRecommended Test Equipment Reporting a ProblemCorrective Actions Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Phase Balancing Voltage Adjustment RangeVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS