Table 1 |
| Alarm Messages - Meaning and Corrective Action (continued) | ||
Alarm |
| Cabinet | Special | Meaning and |
Message |
| Location | Functions | Corrective Action in Brackets [ ] |
BYPASS (Contʼd.) |
|
|
| |
Auto Transfer to |
| SCC | D, E, F | The critical load has been automatically transferred to the bypass |
Bypass |
|
|
| line. |
|
|
|
| [Use the History Status screen to determine the cause for the |
|
|
|
| transfer. Clear all of the alarms before attempting to retransfer the |
|
|
|
| load from bypass to UPS.] |
Auto Retransfer |
| SCC | — | An automatic retransfer will be initiated when the OK to Transfer |
Primed |
|
|
| condition has been present for 10 seconds, if the overload has |
|
|
|
| dropped below 100% of the rated SCC current and if enough UPS |
|
|
|
| modules are |
Manual Reset/ |
| SCC | — | A manual retransfer is required. Either a system overload condition |
Retransfer |
|
|
| has lasted more than 5 minutes, or no more |
|
|
|
| are available. Note that this alarm is only used if |
|
|
|
| attempts are enabled. |
|
|
|
| [Perform a manual retransfer if all necessary conditions are present.] |
Static Switch |
| SCC | S | The UPS output is not synchronized to the bypass power source. |
Unable |
|
|
| The static bypass switch is disconnected, or it has failed internally. |
|
|
|
| [Emergency and overload transfer to the bypass source is not |
|
|
|
| available. Manually set the Static Switch Disconnects to ON (closed) |
|
|
|
| if the static switch is disconnected. If the alarm conditions are |
|
|
|
| automatically corrected, reset the alarm to clear it. Contact Liebert |
|
|
|
| Global Services if the alarm stays on.] |
Bypass Not |
| SCC | — | The bypass power source voltage is not within specifications. |
Available |
|
|
| [Check the bypass power source.] |
Bypass Phase |
| SCC | — | The power conductors on the bypass line are not wired to the UPS in |
Sequence Wrong |
|
| the required sequence. This alarm should appear only during initial | |
|
|
|
| |
|
|
|
| [Disconnect power from the bypass line and correct the wiring. A |
|
|
|
| Liebert Global Services representative must be present during initial |
|
|
|
| |
UPS SYSTEM |
|
|
|
|
Input Current |
| MMU | E | At least one input phase differs from the average current by 10% or |
Unbalanced |
|
|
| more for four (4) hours. Contact Liebert Global Services. If the |
|
|
|
| condition persists, transfer the load to the bypass line. |
Control Power |
| SCC | L, S | The logic control power supply from the UPS output is not operating |
Fail |
| MMU | L, R, S | properly. The UPS module continues operating but will shut down if |
|
|
|
| the input power fails. The SCC continues operating but will shut |
|
|
|
| down if the bypass power fails. Contact Liebert Global Services |
|
|
|
| immediately. |
Output Over/ |
| SCC | L, S | Output frequency differs from the nominal (60 Hz) by more than 0.5 |
Under Frequency |
|
| Hz. No transfer or shutdown occurs. | |
|
|
|
| [Contact Liebert Global Services at once.] |
Output Under- |
| SCC | D, F, L, S | The UPS system output voltage is under the minimum |
Voltage |
|
|
| deviation from nominal. The load automatically transfers to the |
|
|
|
| bypass line. |
|
|
|
| [If the alarm condition is no longer present, reset the alarm and |
|
|
|
| retransfer the load from bypass to UPS. Contact Liebert Global |
|
|
|
| Services if alarm persists.] |
Output Over- |
| SCC | D, F, L, S | The UPS system output voltage is above the maximum (+10%) |
Voltage |
|
|
| deviation from nominal. The load automatically transfers to the |
|
|
|
| bypass line. All UPS modules are taken |
|
|
|
| [Contact Liebert Global Services at once. Do not attempt to reset |
|
|
|
| circuit breakers.] |
Table 1 Abbreviations |
|
| ||
D = | L = latches |
|
| |
E = reports only; | R = remote |
|
| |
F = freezes; | S = summary |
|
|
D* =
D# =