Liebert Series 600T manual MOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings

Page 41

Figure 16 through Figure 20 illustrate how the Monitor/Mimic Display screens on the SCC and on a module depict the power flow through the UPS system.

A three module system designed for redundant operation is shown. A multi-module UPS system may include up to six (6) modules for each System Control Cabinet (SCC).

Figure 16 Monitor/Mimic Display Screen Examples: Normal Power Flow, SCC (above) and Module

BYPASS INPUT A-B B-C C-A 480V 480V 480V

60.0 Hz

UPS INPUT PWR A-B B-C C-A 480V 480V 480V

MOD 1 ON LINE MOD 2 ON LINE MOD 3 ON LINE

UPS RATINGS

SCCB 1600

OUTPUT VOLTAGE

A-B B-C C-A 480V 480V 480V 60.0 Hz

OK to Transfer

Static Switch Connected

LOAD

627 KVA / 502 KW

A B C 755A 755A 755A

3 OF 3 MODULES

CONNECTED REDUNDANT

LOAD

270 KVA / 217 KW

UPS INPUT PWR A-B B-C C-A 480V 480V 480V 350A 350A 350A

BATTERY

VOLTS 540 AMPS 15 CHARG

UPS RATINGS

AP648-84

RATED 400 KVA OUTPUT VOLTAGE A-B B-C C-A 480V 480V 480V 60.0 Hz

A B C 410A 410A 410A

Operation 35

DISCONTINUED

PRODUCT

Image 41
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual Multi-Module UPS, 65-80 kVA left and 100-500 kVA right System DescriptionProduct Multi-Module 500-750 kVA UPS System Control Cabinets SCCs Types of System Control Cabinets SCCsOther Factors to Consider ReliabilityDesigned for Success Safety Precautions Modes of Operation Operator Controls DIS Product Options System Control Cabinet General Component DescriptionsUPS Module Battery PlantControls Hardware Detailed Component DescriptionsFirmware Rectifier/ChargerBattery Charging Circuit Input Power FactorInput Circuit Breaker Isolation TransformerBattery Charge Current Limiting Battery DisconnectBattery Equalize Charge Circuit Operation After End-of-DischargeUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Static Switch IsolationFuse Protection Shorted SCR MonitoringLoad Transfers Pulsed Parallel OperationAutomatic Transfers to Bypass Transfer and Retransfer ConditionsManual Transfers Transfer InhibitedRetransfer Inhibited Redundant ModeManual Retransfers Display Screen and Operator Controls FeaturesDescription Function System Control Cabinet Operator Controls Sccb Pictured Description Location Function Shutdown ProceduresSwitches Behind SCC Control Panel Door Menu Tree WALK-IN Display modules only Master Menu ScreenCustomer Alarm Definitions SCC only Load Transfer Procedures SCC onlyBattery Time modules only Output Metering Displays Monitor/Mimic Display ScreenInput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Item 5 Alarm Messages Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen During Start-Up Walk-In Display ScreenStatus Reports Screen Status Reports ScreensSelect Exit Present StatusEvent History MODULE-0 Event HistoryHistory Status Report Screens History StatusModule SCCSystem Status Battery Cycle Monitor Module OnlyBattery Cycle Monitoring Summary Screen System Configuration System Configuration ScreensDate Screen DateTime Screen TimeDial Auto DialModem Baud Rate Modem Baud RateRetransfer Attempts Maximum Auto-Retransfer AttemptsRemote Monitor Alarm Settings Alarm Limit Settings ScreenProduct Refer to 3.3.2 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.3.1 Start-Up Procedure for more details Start-Up Procedures ScreenModule Start- Up Procedures Screen Shutdown Procedures Shutdown Procedures ScreenModule Shutdown Procedures Screen VDC Battery Time Screen Module OnlyBattery Time Screen Example 45 Minute Discharge Aining Rem Tim Calculated La p s e d T im e M in u te s Range of Values for Calculated Battery TimesUP Cursor UP Down Cursor Down Select Choose Meter Calibration ScreenBattery Equalize Recharging Battery Equalize Screen3 Modules Connected Alarm and Status Messages Module Status MessagesLoad Block Messages System Status MessagesOF/UF Abbreviations Used in Alarm MessagesBattery CB Open DC Ground FaultPower BatteryStatic Switch Manual ResetBypass Phase Control PowerIndications and Other Alarms That Activate Summary Alarms AlarmSystem Configuration Screens or the watchdog timer has Reverse PowerOver-Temperature TemperatureTimeout System Configuration Screens Load On UPSSpecial Functions Alarm MessageWorldwide Reporting Communication InterfacesAuto-Dial Requesting InformationLocal Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Scct Load On BypassLoad on Bypass UPS Available OK To TransferLoad on UPS Bypass Available Refer to 3.4 Automatic Operations Momentary OverloadsInput Power Fail Load on Battery Input Power Failure Load On BatteryOne Module Off-Line Load on UPS One Module Off-LineLoad on UPS Battery Not Available Off BatteryEmergency Modules Off Refer to 3.3.3 Shutdown ProceduresEmergency Power Off Emergency Power OffSystem Shutdown Refer to 3.2.10 Maintenance BypassLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Refer to 3.4 Automatic Operations for more details Manual ProceduresStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass System BypassUPS bypass line is still energized Shutdown Procedures System Shutdown Procedure100 Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoOverloads Without Transfer Automatic OperationsAutomatic Retransfers to UPS Automatic Transfers to BypassAutomatic Emergency Modules Off Automatic Module Off-LineMaintenance DIS Product Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Battery Safety Precautions Battery MaintenanceDIS Product 112 DIS Product Power Batteries Matching Battery Cabinets OptionalRack-Mounted Batteries Torque RequirementsDetection of Trouble Torque Specifications Unless Otherwise LabeledRecommended Test Equipment Reporting a ProblemCorrective Actions Rating Environmental Conditions Battery Operation AdjustmentsElectrical Specifications Phase Balancing Voltage Adjustment RangeVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS
Related manuals
Manual 84 pages 39.26 Kb