5.5Electrical Specifications
RECTIFIER INPUT
Input Voltage: | Standard |
| request. |
Voltage Range: | +10%, |
|
|
Frequency Range: | 57 Hz to 63 Hz. |
|
|
Subcycle Magnetization Inrush: | Less than 3 times normal full load input current for UPS models without |
| optional input isolation transformer. Less than 8 times normal full load input |
| current for |
| rectifier. |
Input Current | From 20% to 100% in 15 seconds. |
|
|
Current Limit: | Maximum of 125% normal full load input current. |
|
|
Current Distortion | Less than 30% THD typical at normal full load input current. Less than 7% |
| reflected THD typical at normal full load input current with optional input filter. |
| 500 kVA to 750 kVA models with optional |
| typical at normal full load input current. Less than 4% reflected THD typical at |
| normal full load input current with optional input filter. |
Power Factor | 0.85 minimum lagging at full load. |
| 0.92 minimum lagging at full load with optional input filter. |
BYPASS INPUT |
|
|
|
Input Voltage: | Standard |
| voltages available on request. |
| plus ground. |
| Optional |
| available on request. |
| grounded delta). |
Voltage Range: | ±5% for manually initiated bypass transfer |
| ±10% for automatically initiated uninterrupted transfer. |
Frequency Range: | 59.5 Hz to 60.5 Hz. |
|
|
Voltage Transient: | ±4% for manually initiated bypass transfer. |
|
|
120 | Specifications and Ratings | DISCONTINUED |
|