Liebert Series 600T manual Overload Transfer, Module Summary, Alarm, Module N Off Line, Inverter

Page 78

Table 1

 

Alarm Messages - Meaning and Corrective Action (continued)

Alarm

 

Cabinet

Special

Meaning and

Message

 

Location

Functions

Corrective Action in Brackets [ ]

UPS SYSTEM (Contʼd.)

 

 

Overload

 

SCC

R, S

The UPS output current exceeds the rated system load current. This

 

 

MMU

S

condition causes an alarm only, the UPS does not shut down.

 

 

 

 

[Determine cause of the overload. Reduce the load until the overload

 

 

 

 

condition is corrected. Reset the UPS alarm.]

Overload Transfer

SCC

D, F, L, S

The load on the UPS has exceeded the current versus time window

 

 

 

 

of system overload capacity. The UPS system transfers the load to

 

 

 

 

bypass.

 

 

 

 

[Reduce the load. If the system does not initiate an automatic load

 

 

 

 

retransfer, manually retransfer the critical load from the bypass line

 

 

 

 

to the UPS. Reset the alarm.]

Module Summary

SCC

S

An alarm message (see lists in SCC and Module Remote Monitor

Alarm

 

 

R (MMU)

Indications and Other Alarms That Activate Summary Alarms in

 

 

 

 

3.1.5 - System Configuration Screens) or the watchdog timer has

 

 

 

 

activated the Module Summary Alarm.

 

 

 

 

[Clear alarm conditions, if possible.]

Module N Off Line

SCC

D

The output circuit breaker of Module N is open. The number N will

 

 

 

R (MMU)

identify the module (1 through 6).

 

 

 

 

[Review active alarms at Module N and clear alarm conditions, if

 

 

 

 

possible.]

Inverter

 

MMU

Inverter output is not synchronized with the UPS system critical bus.

Nonsynchronized

 

 

This also means the output circuit breaker is open and should not be

 

 

 

 

closed until the output is in sync. This condition may correct itself. If

 

 

 

 

not, shut down the UPS module and then perform a start-up

 

 

 

 

procedure.

 

 

 

 

[Contact Liebert Global Services if condition persists.]

Overload

 

MMU

D, F, L, S

The UPS output current has exceeded 175% of the rated full load or

Shutdown

 

 

 

the overload capacity has been exceeded. The UPS module is taken

 

 

 

 

off-line and shut down.

 

 

 

 

[Contact Liebert Global Services at once. Do not attempt to reset

 

 

 

 

circuit breakers.]

Reverse Power

 

MMU

D, F, L, S

Excessive reverse power flow from the critical bus into the UPS

 

 

 

 

inverter has occurred, probably because of low inverter output

 

 

 

 

voltage or a phase mismatch. The UPS module is taken off-line and

 

 

 

 

is shut down.

 

 

 

 

[Contact Liebert Global Services immediately. Do not attempt to

 

 

 

 

reset circuit breakers.]

Inverter Fault

 

MMU

D, F, S

At least one of the fuses has opened or an inverter fault was

 

 

 

 

detected. The UPS module is taken off-line and is shut down.

 

 

 

 

[Contact Liebert Global Services immediately. Do not attempt to

 

 

 

 

reset the circuit breakers.]

Communication

 

SCC

S

The COM FAIL status message is as important as an alarm

Failure

 

 

 

message. Refer to 3.1.13 - Alarm and Status Messages.

Battery Cycle

 

D, E

The optional Battery Cycle Monitor can retain information about the

Buffer Warning

 

 

 

last 132 battery discharge events. When the storage buffer

 

 

 

 

approaches its capacity, this warning message is broadcast via

 

 

 

 

terminal and modem communication channels, and a complete

 

 

 

 

listing of all records is sent to the terminal port. The message clears

 

 

 

 

after 30 seconds.

Table 1 Abbreviations

 

 

 

D = auto-dial;

L = latches

 

 

E = reports only;

R = remote

 

 

F = freezes;

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

72

Operation

DISCONTINUED

 

 

PRODUCT

Image 78
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual System Description Multi-Module UPS, 65-80 kVA left and 100-500 kVA rightProduct Multi-Module 500-750 kVA UPS Types of System Control Cabinets SCCs System Control Cabinets SCCsReliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options General Component Descriptions System Control CabinetBattery Plant UPS ModuleFirmware Detailed Component DescriptionsControls Hardware Rectifier/ChargerInput Circuit Breaker Input Power FactorBattery Charging Circuit Isolation TransformerBattery Equalize Charge Circuit Battery DisconnectBattery Charge Current Limiting Operation After End-of-DischargeInverter Non-Linear Load CharacteristicsUnbalanced Load Characteristics Output Regulation and Overload PerformanceFuse Protection Static Switch IsolationStatic Bypass Shorted SCR MonitoringPulsed Parallel Operation Load TransfersManual Transfers Transfer and Retransfer ConditionsAutomatic Transfers to Bypass Transfer InhibitedRedundant Mode Manual RetransfersRetransfer Inhibited Features Display Screen and Operator ControlsDescription Function System Control Cabinet Operator Controls Sccb Pictured Shutdown Procedures Description Location FunctionSwitches Behind SCC Control Panel Door Menu Tree Master Menu Screen WALK-IN Display modules onlyLoad Transfer Procedures SCC only Battery Time modules onlyCustomer Alarm Definitions SCC only Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 5 Module Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Alarm Messages Item 5 Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen Walk-In Display Screen During Start-UpStatus Reports Screens Status Reports ScreenPresent Status Select ExitEvent History Event History MODULE-0History Status History Status Report ScreensSCC ModuleBattery Cycle Monitor Module Only System StatusBattery Cycle Monitoring Summary Screen System Configuration Screens System ConfigurationDate Date ScreenTime Time ScreenAuto Dial DialModem Baud Rate Modem Baud RateMaximum Auto-Retransfer Attempts Retransfer AttemptsRemote Monitor Alarm Limit Settings Screen Alarm SettingsProduct Load Transfer Procedures Screen Refer to 3.3.2 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.3.1 Start-Up Procedure for more detailsModule Start- Up Procedures Screen Shutdown Procedures Screen Shutdown ProceduresModule Shutdown Procedures Screen Battery Time Screen Module Only VDCBattery Time Screen Example 45 Minute Discharge Range of Values for Calculated Battery Times Aining Rem Tim Calculated La p s e d T im e M in u te sMeter Calibration Screen UP Cursor UP Down Cursor Down Select ChooseBattery Equalize Screen Battery Equalize RechargingAlarm and Status Messages Module Status Messages 3 Modules ConnectedSystem Status Messages Load Block MessagesAbbreviations Used in Alarm Messages OF/UFPower DC Ground FaultBattery CB Open BatteryBypass Phase Manual ResetStatic Switch Control PowerSystem Configuration Screens or the watchdog timer has AlarmIndications and Other Alarms That Activate Summary Alarms Reverse PowerTimeout TemperatureOver-Temperature System Configuration Screens Load On UPSAlarm Message Special FunctionsAuto-Dial Communication InterfacesWorldwide Reporting Requesting InformationSite Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Remote Monitor PanelSeparate / Simultaneous Outputs Load On Bypass ScctOK To Transfer Load on Bypass UPS AvailableLoad on UPS Bypass Available Momentary Overloads Refer to 3.4 Automatic OperationsInput Power Failure Load On Battery Input Power Fail Load on BatteryOne Module Off-Line One Module Off-Line Load on UPSOff Battery Load on UPS Battery Not AvailableRefer to 3.3.3 Shutdown Procedures Emergency Modules OffEmergency Power Off Emergency Power OffRefer to 3.2.10 Maintenance Bypass System ShutdownLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Manual Procedures Refer to 3.4 Automatic Operations for more detailsStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures If the load is on Maintenance Bypass Maintenance Bypass Load TransfersMaintenance Bypass System BypassShutdown Procedures System Shutdown Procedure UPS bypass line is still energized100 Module Shutdown Procedure Remote Emergency Power Off Repo Local Emergency Modules Off LemoAutomatic Operations Overloads Without TransferAutomatic Transfers to Bypass Automatic Retransfers to UPSAutomatic Module Off-Line Automatic Emergency Modules OffMaintenance DIS Product Professional Start-Up Liebert Global ServicesMaintenance Agreements The Signature Program TrainingRoutine Maintenance Record LogAir Filters Battery Maintenance Battery Safety PrecautionsDIS Product 112 DIS Product Rack-Mounted Batteries Matching Battery Cabinets OptionalPower Batteries Torque RequirementsTorque Specifications Unless Otherwise Labeled Detection of TroubleReporting a Problem Corrective ActionsRecommended Test Equipment Rating Environmental Conditions Adjustments Battery OperationElectrical Specifications Voltage Transient Recovery Time Voltage Adjustment RangePhase Balancing Voltage Harmonic ContentSeries 600T UPS
Related manuals
Manual 84 pages 39.26 Kb