Liebert Series 600T manual Present Status, Select Exit

Page 48

Present Status

The Present Status screen shows the current status of the UPS system (SCC) or module. This screen displays any alarm messages that are present and the values of the metered parameters for each cabinet. Battery values are dis- played only at the UPS modules.

Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the upper right corner. The Present Status screen display is updated every two seconds.

Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge. The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time Remaining is displayed, and updated every six seconds.

All the information on this screen, including Battery Time Remaining, is available to a local terminal or modem through the communications ports provided in the Series 600T UPS. Refer to Table 3 in this manual for key- board commands to use with the communication ports.

Figure 23 Present Status Report Screens, SCC (above) and Module

PRESENT STATUS

 

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS ****

Batt Discharging

 

 

 

 

 

 

 

 

OUTPUT VOLTS

 

A

B

C

DC

LOAD

HERTZ

TIME

 

 

480

480

480

 

 

 

 

 

 

 

 

OUTPUT AMPS

 

325

325

325

 

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

 

 

270

0:06

 

 

LOAD KVA

 

0

0

0

 

 

 

 

 

BYPASS VOLTS

 

 

 

 

 

 

 

 

 

END OF REPORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESENT STATUS

 

MODULE-0

01/12/98

14:06:26

FRAME 35

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

 

 

 

 

 

OUTPUT VOLTS

 

A

B

C

DC

LOAD

HERTZ

TIME

 

 

480

480

480

 

 

 

 

 

 

 

OUTPUT AMPS

 

325

325

325

 

 

60.0

 

 

 

OUTPUT FREQUENCY

 

 

 

480

 

 

0:09

 

 

BATTERY VOLTS

 

 

 

 

 

 

 

 

 

 

BATTERY AMPS

 

0

0

0

-645

 

 

 

 

 

 

 

INPUT VOLTS

 

 

 

 

 

 

 

 

 

INPUT AMPS

 

0

0

0

 

270

 

 

 

 

 

LOAD KVA

 

 

 

 

 

 

 

 

 

 

END OF REPORT

SELECT : EXIT

42

Operation

DISCONTINUED

 

 

PRODUCT

Image 48
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual System Description Multi-Module UPS, 65-80 kVA left and 100-500 kVA rightProduct Multi-Module 500-750 kVA UPS Types of System Control Cabinets SCCs System Control Cabinets SCCsReliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options General Component Descriptions System Control CabinetBattery Plant UPS ModuleDetailed Component Descriptions Controls HardwareFirmware Rectifier/ChargerInput Power Factor Battery Charging CircuitInput Circuit Breaker Isolation TransformerBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-DischargeNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Isolation Static BypassFuse Protection Shorted SCR MonitoringPulsed Parallel Operation Load TransfersTransfer and Retransfer Conditions Automatic Transfers to BypassManual Transfers Transfer InhibitedRedundant Mode Manual RetransfersRetransfer Inhibited Features Display Screen and Operator ControlsDescription Function System Control Cabinet Operator Controls Sccb Pictured Shutdown Procedures Description Location FunctionSwitches Behind SCC Control Panel Door Menu Tree Master Menu Screen WALK-IN Display modules onlyLoad Transfer Procedures SCC only Battery Time modules onlyCustomer Alarm Definitions SCC only Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Alarm Messages Item 5 Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen Walk-In Display Screen During Start-UpStatus Reports Screens Status Reports ScreenPresent Status Select ExitEvent History Event History MODULE-0History Status History Status Report ScreensSCC ModuleBattery Cycle Monitor Module Only System StatusBattery Cycle Monitoring Summary Screen System Configuration Screens System ConfigurationDate Date ScreenTime Time ScreenAuto Dial DialModem Baud Rate Modem Baud RateMaximum Auto-Retransfer Attempts Retransfer AttemptsRemote Monitor Alarm Limit Settings Screen Alarm SettingsProduct Load Transfer Procedures Screen Refer to 3.3.2 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.3.1 Start-Up Procedure for more detailsModule Start- Up Procedures Screen Shutdown Procedures Screen Shutdown ProceduresModule Shutdown Procedures Screen Battery Time Screen Module Only VDCBattery Time Screen Example 45 Minute Discharge Range of Values for Calculated Battery Times Aining Rem Tim Calculated La p s e d T im e M in u te sMeter Calibration Screen UP Cursor UP Down Cursor Down Select ChooseBattery Equalize Screen Battery Equalize RechargingAlarm and Status Messages Module Status Messages 3 Modules ConnectedSystem Status Messages Load Block MessagesAbbreviations Used in Alarm Messages OF/UFDC Ground Fault Battery CB OpenPower BatteryManual Reset Static SwitchBypass Phase Control PowerAlarm Indications and Other Alarms That Activate Summary AlarmsSystem Configuration Screens or the watchdog timer has Reverse PowerTemperature Over-TemperatureTimeout System Configuration Screens Load On UPSAlarm Message Special FunctionsCommunication Interfaces Worldwide ReportingAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Load On Bypass ScctOK To Transfer Load on Bypass UPS AvailableLoad on UPS Bypass Available Momentary Overloads Refer to 3.4 Automatic OperationsInput Power Failure Load On Battery Input Power Fail Load on BatteryOne Module Off-Line One Module Off-Line Load on UPSOff Battery Load on UPS Battery Not AvailableRefer to 3.3.3 Shutdown Procedures Emergency Modules OffEmergency Power Off Emergency Power OffRefer to 3.2.10 Maintenance Bypass System ShutdownLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Manual Procedures Refer to 3.4 Automatic Operations for more detailsStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Load Transfers Maintenance BypassIf the load is on Maintenance Bypass System BypassShutdown Procedures System Shutdown Procedure UPS bypass line is still energized100 Module Shutdown Procedure Remote Emergency Power Off Repo Local Emergency Modules Off LemoAutomatic Operations Overloads Without TransferAutomatic Transfers to Bypass Automatic Retransfers to UPSAutomatic Module Off-Line Automatic Emergency Modules OffMaintenance DIS Product Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Battery Maintenance Battery Safety PrecautionsDIS Product 112 DIS Product Matching Battery Cabinets Optional Power BatteriesRack-Mounted Batteries Torque RequirementsTorque Specifications Unless Otherwise Labeled Detection of TroubleReporting a Problem Corrective ActionsRecommended Test Equipment Rating Environmental Conditions Adjustments Battery OperationElectrical Specifications Voltage Adjustment Range Phase BalancingVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS
Related manuals
Manual 84 pages 39.26 Kb