Step 3. Manually open the UPS input circuit breaker by moving the handle to the OFF position (Figure 8).

Return to the Monitor/Mimic Display to verify status of the circuit breakers. Press the Alarm Reset pad to clear alarm messages.

Step 4. If maintenance is required on the UPS controls, turn the Control Power switch to the OFF position (Figure 8). You may also want to open the Rectifier Input Breaker (RIB), external to the UPS cabinet.

WARNING

LETHAL VOLTAGES ARE PRESENT WITHIN THIS UNIT EVEN WHEN

IT IS NOT ON OR WHEN UTILITY IS NOT BEING SUPPLIED. OBSERVE

ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO

SO COULD RESULT IN SERIOUS INJURY OR DEATH. DO NOT WORK

ON OR OPERATE THIS EQUIPMENT UNLESS YOU ARE FULLY

QUALIFIED TO DO SO!! NEVER WORK ALONE.

Before performing any maintenance on your Liebert Series 600T UPS, observe ALL of the WARNINGS in 4.0 - Maintenance.

Local Emergency Modules Off (LEMO)

The UPS controls at the SCC include an Emergency Module Off pad (Figure 10, item 12). When this guarded pad is pressed, the load is automatically transferred to the bypass line and the module output, battery, and input circuit breakers trip open to isolate and shut down all the UPS modules. Control Power for indicators and alarms remains on.

Remote Emergency Power Off (REPO)

The Remote Emergency Power Off control (REPO) is a switch located remotely from the UPS system. It will normally be in the same room as the critical load equipment.

The Remote Emergency Power Off switch removes all power to the critical load.

When you trip the Remote Emergency Power Off switch, all UPS circuit breakers are opened, including the System Bypass circuit breaker (SBB). All power through the UPS is removed from the load. You will still have power to the UPS controls, and you may have power to the static switch.

102

Operation

DISCONTINUED

 

 

PRODUCT

Image 108
Contents Series 600T UPS DIS Product Table of Contents Manual Procedures Figures Tables Important Safety Instructions Overview of this Manual System Description Multi-Module UPS, 65-80 kVA left and 100-500 kVA rightProduct Multi-Module 500-750 kVA UPS Types of System Control Cabinets SCCs System Control Cabinets SCCsReliability Designed for SuccessOther Factors to Consider Safety Precautions Modes of Operation Operator Controls DIS Product Options General Component Descriptions System Control CabinetBattery Plant UPS ModuleDetailed Component Descriptions Controls HardwareFirmware Rectifier/ChargerInput Power Factor Battery Charging CircuitInput Circuit Breaker Isolation TransformerBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-DischargeNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Switch Isolation Static BypassFuse Protection Shorted SCR MonitoringPulsed Parallel Operation Load TransfersTransfer and Retransfer Conditions Automatic Transfers to BypassManual Transfers Transfer InhibitedRedundant Mode Manual RetransfersRetransfer Inhibited Features Display Screen and Operator ControlsDescription Function System Control Cabinet Operator Controls Sccb Pictured Shutdown Procedures Description Location FunctionSwitches Behind SCC Control Panel Door Menu Tree Master Menu Screen WALK-IN Display modules onlyLoad Transfer Procedures SCC only Battery Time modules onlyCustomer Alarm Definitions SCC only Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Alarm Messages Item 5 Alarm MessagesMOD 1 on Line MOD 2 on Line MOD 3 on Line UPS Ratings UPS Input PWR UPS Ratings UPS Input PWR Bypass Input Load Bypass Input C-A Walk-In Display Screen Walk-In Display Screen During Start-UpStatus Reports Screens Status Reports ScreenPresent Status Select ExitEvent History Event History MODULE-0History Status History Status Report ScreensSCC ModuleBattery Cycle Monitor Module Only System StatusBattery Cycle Monitoring Summary Screen System Configuration Screens System ConfigurationDate Date ScreenTime Time ScreenAuto Dial DialModem Baud Rate Modem Baud RateMaximum Auto-Retransfer Attempts Retransfer AttemptsRemote Monitor Alarm Limit Settings Screen Alarm SettingsProduct Load Transfer Procedures Screen Refer to 3.3.2 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.3.1 Start-Up Procedure for more detailsModule Start- Up Procedures Screen Shutdown Procedures Screen Shutdown ProceduresModule Shutdown Procedures Screen Battery Time Screen Module Only VDCBattery Time Screen Example 45 Minute Discharge Range of Values for Calculated Battery Times Aining Rem Tim Calculated La p s e d T im e M in u te sMeter Calibration Screen UP Cursor UP Down Cursor Down Select ChooseBattery Equalize Screen Battery Equalize RechargingAlarm and Status Messages Module Status Messages 3 Modules ConnectedSystem Status Messages Load Block MessagesAbbreviations Used in Alarm Messages OF/UFDC Ground Fault Battery CB OpenPower BatteryManual Reset Static SwitchBypass Phase Control PowerAlarm Indications and Other Alarms That Activate Summary AlarmsSystem Configuration Screens or the watchdog timer has Reverse PowerTemperature Over-TemperatureTimeout System Configuration Screens Load On UPSAlarm Message Special FunctionsCommunication Interfaces Worldwide ReportingAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Remote Monitor PanelSeparate / Simultaneous Outputs Load On Bypass ScctOK To Transfer Load on Bypass UPS AvailableLoad on UPS Bypass Available Momentary Overloads Refer to 3.4 Automatic OperationsInput Power Failure Load On Battery Input Power Fail Load on BatteryOne Module Off-Line One Module Off-Line Load on UPSOff Battery Load on UPS Battery Not AvailableRefer to 3.3.3 Shutdown Procedures Emergency Modules OffEmergency Power Off Emergency Power OffRefer to 3.2.10 Maintenance Bypass System ShutdownLoad on Maintenance Bypass Two Breakers Load on Maintenance Bypass Three Breakers Manual Procedures Refer to 3.4 Automatic Operations for more detailsStart-Up Procedure SCC Start-Up B2. Set the Static Switch Disconnects OFF open SCC Start-Up Procedures Screen UPS Module Start-Up Module Start-Up Procedures Screen Product Load Transfer Procedures Maintenance Bypass Load Transfers Maintenance BypassIf the load is on Maintenance Bypass System BypassShutdown Procedures System Shutdown Procedure UPS bypass line is still energized100 Module Shutdown Procedure Remote Emergency Power Off Repo Local Emergency Modules Off LemoAutomatic Operations Overloads Without TransferAutomatic Transfers to Bypass Automatic Retransfers to UPSAutomatic Module Off-Line Automatic Emergency Modules OffMaintenance DIS Product Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Battery Maintenance Battery Safety PrecautionsDIS Product 112 DIS Product Matching Battery Cabinets Optional Power BatteriesRack-Mounted Batteries Torque RequirementsTorque Specifications Unless Otherwise Labeled Detection of TroubleReporting a Problem Corrective ActionsRecommended Test Equipment Rating Environmental Conditions Adjustments Battery OperationElectrical Specifications Voltage Adjustment Range Phase BalancingVoltage Transient Recovery Time Voltage Harmonic ContentSeries 600T UPS