3.4Automatic Operations
The Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con- trol logic monitors the performance of the UPS, the availability of power sources, and the current required by the critical load.
The system control logic at the SCC
1.Determines what overload conditions can be sustained without a transfer to bypass.
2.Initiates an automatic transfer to bypass to sustain an overload.
3.Can initiate an automatic retransfer to the UPS after a system overload has been cleared.
4.Initiates an automatic transfer to bypass and emergency module shutdown when a specified UPS fault occurs.
The control logic at each UPS module
1.Determines what overload conditions can be sustained by the module while it is
2.Automatically takes the UPS module off line and initiates an emergency module shutdown when selected UPS faults occur.
3.4.1Overloads (Without Transfer)
The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload condi- tions that remain within (under) the current versus time curve of system overload capacity and the capacity of modules
For high current demands of short duration (momentary overloads) the critical load is supplied simultaneously by both the UPS system and the bypass line. Whenever the critical load requires more than 155% of the capacity of the modules
Whenever an overload condition occurs, you should determine the cause of the overload.
If an overload condition exceeds the UPS system overload capacity or the capacity of the modules
Figure 64 Current-Versus-Time Curves of Module Overload Capacity
Operation 103