Remote Monitor
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer use through a set of contacts on a separate terminal board.
When the New Alarm, System Summary Alarm, or Module Summary Alarm is activated, you can get more information at the Operator Display Panel or through a remote terminal. Refer to 3.1.14 - Communication Interfaces.
.
SCC and Module Remote Monitor Indications
SCC Remote Monitor Indications | Channel | Module Remote Monitor Indications |
Load On UPS | CH1 | Output CB Open |
Load On Bypass | CH2 | Battery CB Open |
Battery Discharging | CH3 | Battery Discharging |
Low Battery Warning | CH4 | Low Battery Warning |
Overload | CH5 | Control Failure |
Ambient | CH6 | Ambient |
System Summary Alarm | CH7 | Module Summary Alarm |
New Alarm | CH8 | New Alarm |
The following alarms, as well as those listed above, will activate the System Summary Alarm or the Module Summary Alarm.
Other Alarms That Activate Summary Alarms
Other Alarms That Activate | Other Alarms That Activate |
System Summary Alarm | Module Summary Alarm |
Control Power Fail | Blower Failed |
Emergency Off | Control Power Fail |
Module Summary Alarm | DC Capacitor Fuse Blown |
Output Over/Under Frequency | DC Ground Fault |
Output | DC |
Output | Emergency Off |
Overload Transfer | Equipment |
Static Switch Unable | Inverter Fault |
| Low Battery Shutdown |
| Overload |
| Overload Shutdown |
| Rectifier Fuse Blown |
| Reverse Power |