3.8WIRING CONNECTION
WARNING!
UPS installation and connection must be performed by qualified service personnel only.
3.8.1Power connections
Input/output and DC connections are provided with compression lugs.
Please refer to chart for torque specifications.
Carefully read the following recommendations before proceeding:
•Ensure that the AC and DC external isolators are OFF and locked to prevent their inadvertent operation.
•Do not close any external isolators prior the commissioning of the equipment.
•The preferred power cable entry location for installation purposes is from the right side of the UPS, either top or bottom.
To facilitate the terminations remove the right side panel in order to access the input/output terminal lugs.
In case of cable entry from the top of the cabinet, remove the cover plate fitted on the roof and provide for a suitable isolated protection cover.
In case of cable entry from the bottom remove cover plate and perform the same procedure.
•If the UPS is installed in such a way that the accessibility to the right side panel is reduced, field wiring connections can be made from the front side by removing the front right side panel protection cover/panel ( D ) as indicated in Fig.
•The input/output cables must be connected in clockwise phase rotation for both Bypass and Rectifier Input Terminals if separate, taking care to avoid risk of short circuit between different poles.
•The grounding and neutral connection of the electrical system must be in accordance with local regulations.
•In case of additional cabinets containing batteries, input/ output transformers, etc, their ground terminals must be connected to the UPS main ground terminal.
•Once the power cables have been connected,
Torque Specifications
Mechanical Compression Lugs
Input / Output / Battery and GND
WIRE SIZE RANGE |
|
|
| WIRE SIZE RANGE |
|
| |
AWG / kcmil | Lb - in | Nm |
| AWG / kcmil | Lb - in | Nm | |
|
|
|
|
|
|
|
|
6 | – 4 | 110 | 12.4 |
| 3/0 – 200 | 250 | 28.2 |
|
|
|
|
|
|
|
|
3 | – 1 | 150 | 19.6 |
| 250 – 350 | 325 | 36.7 |
|
|
|
|
|
|
|
|
1/0 | – 2/0 | 180 | 20.3 |
| 500 – 750 | 375 | 42.4 |
OPM_SGS_ISG_M22_M30_0US_V011.doc | 21/38 | Installation Guide SG Series 225 & 300 kVA |