g

GE

4.1.3Programmable input free contacts

Some programmable UPS functions (indicated in section 4.1), can be activated by closing an external contact, if connected, on:

X1 / 10, 21

or

J2 / 10, 23

User Input 1

(default = Not used)

(RL1)

X1 / 11, 22

or

J2 / 11, 24

User Input 2

(default = Emergency GEN ON)

(RL2)

4.1.4Gen Set Signaling (GEN ON)

If an emergency generator set supplies the UPS in case of Utility Failure and the generator is particularly unstable in frequency, it should be suitable to install the signal “Generator ON” on X1/11, 22 or J2/11, 24 (this input is programmed as default for this function).

When this contact closes, it causes the change of certain functions (programmable) such as:

Enabling or disabling of synchronization and consequently the Load transfer to generator.

Reduction or elimination or delay of Battery recharging during the generator operation.

In a parallel system a separate NO (Normally Open) contact must be connected individually to each unit.

4.1.5AUX external Maintenance Bypass

If the UPS system is equipped with an external Maintenance Bypass Switch, it is possible to connect a NO (normally open) voltage free aux. contact from the External Bypass Switch to the programmable input X1/10-21or J2/10-23, making the UPS operate as if the internal switch Q2 has closed.

This function can be activated by changing a dedicated parameter (password required).

When this NO (Normally Open) contact closes, the output Inverter Contactor K7 it is automatically opened and the Load transfer back to Inverter will be inhibited.

In a parallel system, the input on customer interface of each unit must be connected to a separate AUX contact of the External Maintenance Bypass Switch.

4.1.6Auxiliary Power Supply (APS) 24 VDC / 1A

1

 

 

2

 

 

3

 

1

4

 

XA

2

 

 

3

 

 

 

 

4

XA - 1

24 VDC

XA - 2

GND

XA - 3

24 VDC

XA - 4

GND

Fig. 4.1.6-1 Terminals for connection 24 VDC

OPM_SGS_ISG_M22_M30_0US_V011.doc

36/38

Installation Guide SG Series 225 & 300 kVA

Image 36
Contents SG Series Copyright 2003 by GE Industrial Systems SystemsDear Customer Start UP and CommissioningPreface Table of contents Installation BatteryGeneral StorageSafety instructions when working with battery Safety symbols and warnings Safety warningsRisk of electric shock PE Earth GND Ground Protective Grounding TerminalLayout Layout SG Series 225 and 300 KVADimensions and weight Weight SG Series 225 and 300 kVATransport Forklift Crane Transport UPS only in upright positionStorage of Battery DeliveryStorage of the UPS Place of Installation Positioning of the UPS SG SeriesCheck -26A of the NEC code for specific requirements Openings for input and output cable connections Fixing of the UPS cabinet on the floorBattery location 1-5 RPA system dispositionVentilation and Cooling CFMTake care not to damage the UPS when moving by forklift UnpackingPacking material recycling Electrical Wiring Separate input Rectifier & Bypass recommendedCommon input Rectifier & Bypass Input/output over current protection and wire sizing Neutral current could be greater than the phase currentsPhase, 3 wire plus Ground Phase, 4 wire plus GroundWire positive and negative plus Ground See .7.1-1Copper Wiring Connection Wire Size Range1-1 Access to the input / output connections Power connection with common input utility Common Input Rectifier / BypassOutput Load Cable section for this connection shall be not less then AWG Power connection separate input utility L1-1 Rectifier Phase a L1-2L2-1 Rectifier Phase B L2-2 L3-1 Rectifier Phase C L3-2BR1 Battery connection BatteryPositive pole of the Battery Do not insert the Battery Fuses before the commissioningSetup for SG Series when functioning as frequency converter Manual Bypass, serious damage to the Load could resultPower Wiring of Parallel Units 1 RPA Parallel SystemUPS Parallel Control BUS ConnectionTerminal units Intermediate unitsAccess to the control bus connection Control BUS Cable LocationControl bus cables connection Interface IM0048 going to P13Control bus cables routing 11-3 Control Bus cable routing and connectionCustomer Interface Customer Interface15, 16 Or J2 17, 18 NO, C, NC General Alarm 18, 19 Or J2 20, 21 NO, C, NC Acoustic AlarmOutput potential free contacts Or J2 / 1, 2 NO, C, NC Utility FailureGND EPO Emergency Power Off Input contact JP338/38