3.8.5Setup for SG Series when functioning as frequency converter

When the SG Series is utilized for different output frequency compared to the input frequency, the Automatic Bypass and Manual Bypass functions are disabled, therefore the Load cannot be transferred to Utility in case of overload, short circuit, or inverter failure.

In situations where the UPS needs to be powered down for maintenance purposes, the critical Load must also be powered down during this time, the UPS cannot be transferred to

Manual Bypass, serious damage to the Load could result.

Circuit breaker Q2 - Manual Bypass must be blocked in the open position, to avoid any accidental closure, by means of a padlock or a similar device, when the UPS is used as a frequency converter.

As an added measure of safety the bus bar connections BR1, BR2 and BR3 should also be removed.

See Fig. 3.8.3-2.

Q1

Q2

SGS_225-300_Switches Q2_01

Fig. 3.8.5-1 Switch Q2 – Manual Bypass

NOTE !

The standard SG Series UPS may be operated at 50Hz input with 60Hz output frequency conversion.

It is recommended that the static switch bypass be electronically blocked if the UPS is to operated as a frequency converter in order to prevent damage to the load.

Check with a Global Services Field Service Engineer to facilitate the parameter change.

CAUTION !

The output transformer of the UPS is designed for 60Hz only. Operation at 50Hz, 480V output may overheat the transformer. The optional 5th harmonic filter is designed for 60Hz operation.

If the UPS is purchased with this internal filter it may not be operated at 50Hz input or damage to the filter could result.

OPM_SGS_ISG_M22_M30_0US_V011.doc

28/38

Installation Guide SG Series 225 & 300 kVA

Image 28
Contents SG Series Copyright 2003 by GE Industrial Systems SystemsDear Customer Start UP and CommissioningPreface Table of contents Installation BatteryGeneral StorageSafety instructions when working with battery Safety symbols and warnings Safety warningsRisk of electric shock PE Earth GND Ground Protective Grounding TerminalLayout Layout SG Series 225 and 300 KVADimensions and weight Weight SG Series 225 and 300 kVATransport Forklift Crane Transport UPS only in upright positionDelivery Storage of BatteryStorage of the UPS Positioning of the UPS SG Series Place of InstallationCheck -26A of the NEC code for specific requirements Openings for input and output cable connections Fixing of the UPS cabinet on the floorBattery location 1-5 RPA system dispositionVentilation and Cooling CFMUnpacking Take care not to damage the UPS when moving by forkliftPacking material recycling Separate input Rectifier & Bypass recommended Electrical WiringCommon input Rectifier & Bypass Input/output over current protection and wire sizing Neutral current could be greater than the phase currentsPhase, 3 wire plus Ground Phase, 4 wire plus GroundWire positive and negative plus Ground See .7.1-1Copper Wiring Connection Wire Size Range1-1 Access to the input / output connections Common Input Rectifier / Bypass Power connection with common input utilityOutput Load Cable section for this connection shall be not less then AWG Power connection separate input utility L1-1 Rectifier Phase a L1-2L2-1 Rectifier Phase B L2-2 L3-1 Rectifier Phase C L3-2BR1 Battery connection BatteryPositive pole of the Battery Do not insert the Battery Fuses before the commissioningSetup for SG Series when functioning as frequency converter Manual Bypass, serious damage to the Load could resultPower Wiring of Parallel Units 1 RPA Parallel SystemUPS Parallel Control BUS ConnectionTerminal units Intermediate unitsAccess to the control bus connection Control BUS Cable LocationControl bus cables connection Interface IM0048 going to P13Control bus cables routing 11-3 Control Bus cable routing and connectionCustomer Interface Customer Interface15, 16 Or J2 17, 18 NO, C, NC General Alarm 18, 19 Or J2 20, 21 NO, C, NC Acoustic AlarmOutput potential free contacts Or J2 / 1, 2 NO, C, NC Utility FailureGND EPO Emergency Power Off Input contact JP338/38