GE 300, 225 manual Power Wiring of Parallel Units, RPA Parallel System

Page 29

g

GE

3.9POWER WIRING OF PARALLEL UNITS

To guarantee good Load sharing between the units of a parallel system, we recommend it is recommended that the cable length from the input distribution board (5) to the output distribution board (10) are the same length for each unit (a+b = c+d = e+f = g+h = i+l = m+n = o+p = q+r). Tolerance: +/-10%.

The AC input power of the Bypass must be the same for all units of the parallel system - no phase shift allowed between units.

It is strongly recommended that no transformers, automatic circuit breakers or fuses should be inserted between the unit’s output and the Load common bus bars.

However, it is recommended that a disconnect or isolation switch be inserted in order to totally isolate a unit if needed

Verify that power wiring and control wiring are run in separate conduits or cable trays. UPS input cables must be run in separate conduits from the output cables.

Fig. 3.9-1 RPA Parallel System

1 = Rectifier

2 = Inverter

3= Electronic Bypass

4= Manual Bypass

5= Input Utility Distribution

6= Unit Output Load

7= External Battery MCB

8= External Battery fuse

9= External Battery

10= Common Busbar and Output Load Distribution

c= Unit Number 1

2

=

Unit Number 2

3

=

Unit Number 3

4

=

Unit Number 4

5

=

Unit Number 5

6

=

Unit Number 6

7

=

Unit Number 7

8

=

Unit Number 8

In a RPA configuration with 3-wire kit, it’s most important to connect the Neutrals of the UPS outputs together (see Fig .3.8.2-2 and 3.8.3-2). Cable section for this connection shall be not less then AWG 1

OPM_SGS_ISG_M22_M30_0US_V011.doc

29/38

Installation Guide SG Series 225 & 300 kVA

Image 29
Contents SG Series Systems Copyright 2003 by GE Industrial SystemsStart UP and Commissioning Dear CustomerPreface Table of contents Battery InstallationGeneral StorageSafety instructions when working with battery Safety warnings Safety symbols and warningsRisk of electric shock PE Earth GND Ground Protective Grounding TerminalLayout SG Series 225 and 300 KVA LayoutWeight SG Series 225 and 300 kVA Dimensions and weightTransport Forklift Crane Transport UPS only in upright positionStorage of the UPS Storage of BatteryDelivery Check -26A of the NEC code for specific requirements Place of InstallationPositioning of the UPS SG Series Fixing of the UPS cabinet on the floor Openings for input and output cable connections1-5 RPA system disposition Battery locationCFM Ventilation and CoolingPacking material recycling Take care not to damage the UPS when moving by forkliftUnpacking Common input Rectifier & Bypass Electrical WiringSeparate input Rectifier & Bypass recommended Neutral current could be greater than the phase currents Input/output over current protection and wire sizingPhase, 4 wire plus Ground Phase, 3 wire plus GroundWire positive and negative plus Ground See .7.1-1Copper Wire Size Range Wiring Connection1-1 Access to the input / output connections Output Load Power connection with common input utilityCommon Input Rectifier / Bypass Cable section for this connection shall be not less then AWG L1-1 Rectifier Phase a L1-2 Power connection separate input utilityL2-1 Rectifier Phase B L2-2 L3-1 Rectifier Phase C L3-2BR1 Battery Battery connectionPositive pole of the Battery Do not insert the Battery Fuses before the commissioningManual Bypass, serious damage to the Load could result Setup for SG Series when functioning as frequency converter1 RPA Parallel System Power Wiring of Parallel UnitsParallel Control BUS Connection UPSIntermediate units Terminal unitsControl BUS Cable Location Access to the control bus connectionControl bus cables connection Interface IM0048 going to P1311-3 Control Bus cable routing and connection Control bus cables routingCustomer Interface Customer Interface18, 19 Or J2 20, 21 NO, C, NC Acoustic Alarm 15, 16 Or J2 17, 18 NO, C, NC General AlarmOutput potential free contacts Or J2 / 1, 2 NO, C, NC Utility FailureGND JP3 EPO Emergency Power Off Input contact38/38