4 CUSTOMER INTERFACE

GE

4.1CUSTOMER INTERFACE

4

3

2

1

 

XA

 

 

 

12

1

 

 

 

 

13

2

J5

 

 

 

14

3

 

 

 

 

 

 

 

15

4

 

 

 

 

16

5

 

 

 

 

17 18

6 7

X1

 

 

 

19

8

 

 

 

 

20

9

 

 

 

 

21 22

10 11

 

 

 

 

1

 

 

 

 

 

2

JP3

 

 

 

 

 

 

 

 

J2

J4

 

 

 

 

interface01

 

 

14

1

 

 

 

9

 

J3

300- Customer

 

 

1

 

 

 

 

 

 

SGS 225

4

3

2

1

 

 

 

 

 

 

 

XB

Fig. 4.1-1 Customer interface

Serial port J3 - RS 232 (sub D - female 9 pin)

Suitable for JUMP protocol

Pin 2: TX (out)

 

Pin 3: RX (in)

Pin 5: GND

 

J2 (subD-female 25p) – Output signals on voltage free contacts

J2/1, 2, 3

-

NO, C, NC

-

Utility Failure

(def. Param. RL=1)

J2/4, 5, 6

-

NO, C, NC

-

Load on Inverter

(def. Param. RL=3)

J2/7, 8, 9

-

NO, C, NC

-

Stop Operation

(def. Param. RL=5)

J2/14, 15, 16

-

NO, C, NC

-

Load on Utility

(def. Param. RL=2)

J2/17, 18, 19

-

NO, C, NC

-

General Alarm

(def. Param. RL=4)

J2/20, 21, 22

-

NO, C, NC

-

Acoustic Alarm

(def. Param. RL=6)

Signals on terminals X1 and on connector J2 are in parallel and therefore not separated galvanically from each other.

The programmable signals on X1 and J2 will be disabled with Q1 open, with the exception of the signals for “16 - Manual Bypass ON” and “26 - EPO”.

XB - Terminals for EPO connection

X2 / 1, 2 or J2 / 12, 25NC EPO (Emergency Power Off)

Note: to enable this function, remove cable short-circuiting XB / 2 – 3 and the Jumper JP3 on P4 – Customer Interface.

X1 – Output signals on voltage free contacts - terminals

X1/1, 2, 3

-

NO, C, NC

-

Utility Failure

(def. Param. RL=1)

X1/4, 5, 6

-

NO, C, NC

-

Load on Inverter

(def. Param. RL=3)

X1/7, 8, 9

-

NO, C, NC

-

Stop Operation

(def. Param. RL=5)

X1/12, 13, 14

-

NO, C, NC

-

Load on Utility

(def. Param. RL=2)

X1/15, 16, 17

-

NO, C, NC

-

General Alarm

(def. Param. RL=4)

X1/18, 19, 20

-

NO, C, NC

-

Acoustic Alarm

(def. Param. RL=6)

Input contacts

X1/10, 21 or J2/10, 23

Programmable (default = RL1)

X1/11, 22 or J2/11, 24

Programmable / Generator ON (NO) (def. = RL2)

NO = normally open

C = common

NC = normally closed

The connectors J4 and J5 can be used for additional SNMP Card, Environmental Card (not available yet) or an additional Customer Interface (installation only when the UPS is switched Off).

XA: terminals for 24VDC Auxiliary Power Supply connection.

XB: terminals for EPO connection.

 

 

 

 

 

 

Programmable user relays

 

Programmable functions on contacts (X1 - J2)

 

On terminals X1 or J2 connector, six of the following 26

 

Some UPS functions can be activated with

 

signals can be selected from the display, entering with the

 

parameters when an external Normally Open

 

appropriate password.

 

 

contact is closed on:

 

 

0- No Information

14- Rectifier Utility Failure

 

 

 

 

X1-10, 21 / J2-10, 23

or X1-11, 22 / J2- 11, 24

 

1- Buzzer

15- Battery Discharge

 

 

 

Selectable functions by changing parameters

 

2- General Alarm

16- Manual Bypass ON

 

 

3- Load on Utility

17- Rectifier ON

 

(password required) are:

 

4- Stop Operation

18- Inverter ON

 

0 - No function

1 - Inverter ON

 

5- Load on Inverter

19- Boost Charge

 

2 - Inverter OFF

3 - Print All

 

6- Utility Failure

20- Battery Earth Fault

 

4 - Status Relay

5 - Generator ON

 

7- DC Over Voltage

21- Battery Fault

 

6 - External Bypass ON

 

8- Low Battery

22- Relay Input 1

 

 

 

7 - External Battery Fuses, or External K3.

 

9- Overload

23- Relay Input 2

 

 

 

 

See Alarm 4104 - “Battery Fuses”.

 

10- Over Temperature

24- Relay Output ON

 

 

 

 

Voltage free contacts: Max. DC / AC: 24V / 1.25A

 

11- Inverter-Utility not syncr.

25- Relay Output OFF

 

 

12- Bypass Locked

26- EPO (Emergency

 

 

 

IEC 950 (SELV circuit)

 

13- Bypass Utility Failure

Power Off)

 

 

 

Min. Signal Level: 5VDC/50mA

OPM_SGS_ISG_M22_M30_0US_V011.doc

34/38

Installation Guide SG Series 225 & 300 kVA

Image 34
Contents SG Series Copyright 2003 by GE Industrial Systems SystemsDear Customer Start UP and CommissioningPreface Table of contents General InstallationBattery StorageSafety instructions when working with battery Risk of electric shock PE Earth GND Ground Safety symbols and warningsSafety warnings Protective Grounding TerminalLayout Layout SG Series 225 and 300 KVATransport Forklift Crane Dimensions and weightWeight SG Series 225 and 300 kVA Transport UPS only in upright positionDelivery Storage of BatteryStorage of the UPS Positioning of the UPS SG Series Place of InstallationCheck -26A of the NEC code for specific requirements Openings for input and output cable connections Fixing of the UPS cabinet on the floorBattery location 1-5 RPA system dispositionVentilation and Cooling CFMUnpacking Take care not to damage the UPS when moving by forkliftPacking material recycling Separate input Rectifier & Bypass recommended Electrical WiringCommon input Rectifier & Bypass Input/output over current protection and wire sizing Neutral current could be greater than the phase currentsWire positive and negative plus Ground Phase, 3 wire plus GroundPhase, 4 wire plus Ground See .7.1-1Copper Wiring Connection Wire Size Range1-1 Access to the input / output connections Common Input Rectifier / Bypass Power connection with common input utilityOutput Load Cable section for this connection shall be not less then AWG L2-1 Rectifier Phase B L2-2 Power connection separate input utilityL1-1 Rectifier Phase a L1-2 L3-1 Rectifier Phase C L3-2BR1 Positive pole of the Battery Battery connectionBattery Do not insert the Battery Fuses before the commissioningSetup for SG Series when functioning as frequency converter Manual Bypass, serious damage to the Load could resultPower Wiring of Parallel Units 1 RPA Parallel SystemUPS Parallel Control BUS ConnectionTerminal units Intermediate unitsControl bus cables connection Access to the control bus connectionControl BUS Cable Location Interface IM0048 going to P13Control bus cables routing 11-3 Control Bus cable routing and connectionCustomer Interface Customer InterfaceOutput potential free contacts 15, 16 Or J2 17, 18 NO, C, NC General Alarm18, 19 Or J2 20, 21 NO, C, NC Acoustic Alarm Or J2 / 1, 2 NO, C, NC Utility FailureGND EPO Emergency Power Off Input contact JP338/38