3.2DELIVERY

When delivered, inspect the package integrity and the physical conditions of the cabinets carefully.

In case of any damage sustained during transport, immediately inform the carrier and contact your local Service Center.

A detailed report of the damage is necessary for any insurance claim.

A DAMAGED UPS MUST NEVER BE INSTALLED OR CONNECTED TO UTILITY OR BATTERY!

3.3STORAGE

3.3.1Storage of the UPS

The UPS is carefully packed for transport and storage so that it is in perfect condition when installed.

Never leave a UPS outside the building and don’t store other packages on the top of the UPS.

It is advisable to store the UPS in its original package in a dry, dust-free room, away from chemical substances, and with a temperature range not exceeding -13°F(-25°C) to 131°F (55°C).

Some important functions of the UPS, such as the customized functions, are defined by parameters stored in a RAM memory.

A small backup Battery located on the Control Unit board supplies the RAM.

If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized Service Center before putting the UPS into operation.

3.3.2Storage of Battery

When the delivery includes a maintenance free Battery, keep in mind that they are subject to self-discharge and therefore you must recharge the Battery.

The storage time without Battery recharge depends on the temperature of the storage site.

The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C).

Recharge stored maintenance free Battery every:

6 months when the storage temperature is 68°F (20°C)

3 months when the storage temperature is 86°F (30°C)

2 months when the storage temperature is 95°F (35°C)

OPM_SGS_ISG_M22_M30_0US_V011.doc

11/38

Installation Guide SG Series 225 & 300 kVA

Image 11
Contents SG Series Systems Copyright 2003 by GE Industrial SystemsStart UP and Commissioning Dear CustomerPreface Table of contents Storage InstallationBattery GeneralSafety instructions when working with battery Protective Grounding Terminal Safety symbols and warningsSafety warnings Risk of electric shock PE Earth GND GroundLayout SG Series 225 and 300 KVA LayoutTransport UPS only in upright position Dimensions and weightWeight SG Series 225 and 300 kVA Transport Forklift CraneStorage of the UPS Storage of BatteryDelivery Check -26A of the NEC code for specific requirements Place of InstallationPositioning of the UPS SG Series Fixing of the UPS cabinet on the floor Openings for input and output cable connections1-5 RPA system disposition Battery locationCFM Ventilation and CoolingPacking material recycling Take care not to damage the UPS when moving by forkliftUnpacking Common input Rectifier & Bypass Electrical WiringSeparate input Rectifier & Bypass recommended Neutral current could be greater than the phase currents Input/output over current protection and wire sizingSee .7.1-1 Phase, 3 wire plus GroundPhase, 4 wire plus Ground Wire positive and negative plus GroundCopper Wire Size Range Wiring Connection1-1 Access to the input / output connections Output Load Power connection with common input utilityCommon Input Rectifier / Bypass Cable section for this connection shall be not less then AWG L3-1 Rectifier Phase C L3-2 Power connection separate input utilityL1-1 Rectifier Phase a L1-2 L2-1 Rectifier Phase B L2-2BR1 Do not insert the Battery Fuses before the commissioning Battery connectionBattery Positive pole of the BatteryManual Bypass, serious damage to the Load could result Setup for SG Series when functioning as frequency converter1 RPA Parallel System Power Wiring of Parallel UnitsParallel Control BUS Connection UPSIntermediate units Terminal unitsInterface IM0048 going to P13 Access to the control bus connectionControl BUS Cable Location Control bus cables connection11-3 Control Bus cable routing and connection Control bus cables routingCustomer Interface Customer InterfaceOr J2 / 1, 2 NO, C, NC Utility Failure 15, 16 Or J2 17, 18 NO, C, NC General Alarm18, 19 Or J2 20, 21 NO, C, NC Acoustic Alarm Output potential free contactsGND JP3 EPO Emergency Power Off Input contact38/38