3.9. Monitoring and Relay Output Connections

Front Panel DB9 Connection

The front panel DB-9 connector is used to hook up a standard serial cable for the APC proprietary GUI that will be introduced at a later date. Do not hook up the special RS-232 cable (APC part number 940-0024C). This cable is only to be used with the DB-9 near the Web/SNMP card.

“Smart” Cable DB9 Connection

The DB9 connector on the top right hand side of the unit uses the special RS-232 cable (APC part number 940-0024C) to allow local access through a Terminal Emulation program like HyperTerminal™ or Procomm™ (**).

RJ45 Ethernet Connector

The optional management card has an RJ-45 connector to support a TCP/IP protocol over a 10BaseT Ethernet Local Area Network (LAN).

Relay Output Connections

There are eight alarms available that provide outputs via Form “C” relay contacts. The last two of these are preassigned as the Minor and Major relay outputs. The Major relay is energized (NO-C contacts closed) during normal (non-alarm) operating conditions; all the other relays energize when an alarm condition occurs. The other six outputs are initially designated as “Relay 1” through “Relay 6” (the user may assign more meaningful names if desired). The various system alarm conditions can be assigned to any of the eight alarm outputs. Connectors J1 and J2 are located on the interface card mounted in the top left side of the unit. Refer to the board layout in Figure 3.8-3for Output Relay connections. The relay contacts should only be used to switch resistive loads of 0.5 amperes or less at 60 volts or less. The following shows the alarm output connection designations.

Page 18

MX28B200/400 –48 VDC User’s Manual (990-9133)

Image 24
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionPage Safety First General PrecautionsPage Introduction General Information2 MX28B Block Diagram How to Use This Manual Page Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Power Connections VentilationBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation DC System GroundingDC Power Output Over-Current Protection DC Circuit Breakers#10 studs on 5/8 centers DC GMT Fuses Fuse Rating Part NumberInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationGMT Fuse Installation Load ConnectionsCable Size Considerations Circuit Breaker Connections 1 to 50 AmpsCircuit Breaker Connections 60-100 Amps 1 Standard lug for 1 to 50A breakersGMT Fuse Connections 2 Adaptor and lugs for 60-100 Amp breakersRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Full System Power Up Operation Technical DescriptionRectifier Management System Management System Output CapacitySystem Voltage Control System CurrentBattery Management System Status and Alarm ReportingBattery Charging and Protection DC DistributionControls and Indicators Battery Temperature CompensationBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Batt Disc Alm m+ MinorBatt Disc Thr m+ 10 aCir Bkr 48VCir Bkr 1 Alm m+ MajorFW Version 000189GMT 1 Alm GMT 8 AlmEnable LVD ResetIn-Rly 1 Alm IgnoreOEM S Offset Out-Rly 1 Alm m+Out-Rly 6 Alm m+ Out-RlyRectFailComm MinRect Cfg Alm Rect CL AlmDisable Rect 1 FFRect 1 RFA Rect RFA AlmSys LT Thr Sys LV AlmSys LV Thr 50.00SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysPage Command and Monitoring Protocol Remote MonitoringDescription Physical ConnectionsPage Specifications AC Input1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersRectifiers PscuPower Shelf Control Unit MechanicalMounting Environmental CompliancePage APC Worldwide Customer Support Page Warranty General Provisions