4.3. System Management

System Output Capacity

The power plant has two basic configurations:

The MX28B-200 supplies a maximum of 200 amps or 150 amps with N+1 redundancy. The housing for this configuration provides space for one rectifier shelf that can hold up to four rectifiers, a control unit, and one tier of up to 24 distribution circuit breakers.

The MX28B-400 supplies a maximum of 400 amps or 350 amps with N+1 redundancy. The housing for this configuration provides space for two rectifier shelves that can hold up to four rectifiers each, a control unit, and one tier of up to 24 distribution circuit breakers. The differences between the 200 and 400 amp units are the exterior housing, 50-conductor ribbon cable and an additional rectifier shelf; all other parts are the same for both configurations.

System Voltage Control

The PSCU monitors and adjusts the system voltage. It uses a voltage trim input to the rectifier to precisely control the DC output voltage. In the event of PSCU removal or failure, the shelf rectifier controller card will control the voltage at a programmed default level. In the event of shelf rectifier controller card failure, the individual rectifiers will default to the analog voltage level preset with the front panel “float’ adjustment pots.

System Current

The PSCU monitors individual rectifier currents and displays total system current as a sum of rectifier currents. Load current can be found by adding battery current to system current. Battery Current is positive when the battery is discharging.

Sys Current + Batt current = Load Current

For example, if the battery is charging the Batt Current reading could be (–) 40 A, Sys Current reading could be 120 A. Load Current would be:

Sys Current + Batt current = Load Current 120A + (-) 40 A = 80 Amps.

If the battery is discharging the Batt Current reading would be 40 A, Sys Current would reading would be 40 A. Load voltage would be:

Sys Current + Batt current = Load Current 40A + 40 A = 80 Amps.

Page 24

MX28B200/400 –48 VDC User’s Manual (990-9133)

Image 30
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionPage Safety First General PrecautionsPage Introduction General Information2 MX28B Block Diagram How to Use This Manual Page Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation DC System GroundingDC Power Output Over-Current Protection DC Circuit Breakers#10 studs on 5/8 centers DC GMT Fuses Fuse Rating Part NumberInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationCable Size Considerations GMT Fuse InstallationLoad Connections Circuit Breaker Connections 1 to 50 AmpsCircuit Breaker Connections 60-100 Amps 1 Standard lug for 1 to 50A breakersGMT Fuse Connections 2 Adaptor and lugs for 60-100 Amp breakersFront Panel DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Smart Cable DB9 ConnectionExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Full System Power Up Operation Technical DescriptionRectifier Management System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsBattery Temperature Compensation Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Batt Disc Thr m+ Batt Disc Alm m+Minor 10 aCir Bkr 1 Alm m+ Cir Bkr48V MajorGMT 1 Alm FW Version000189 GMT 8 AlmIn-Rly 1 Alm EnableLVD Reset IgnoreOut-Rly 6 Alm m+ OEM S OffsetOut-Rly 1 Alm m+ Out-RlyRect Cfg Alm RectFailCommMin Rect CL AlmRect 1 RFA DisableRect 1 FF Rect RFA AlmSys LV Thr Sys LT ThrSys LV Alm 50.00SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysPage Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsPage 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersRectifiers PscuPower Shelf Control Unit MechanicalMounting Environmental CompliancePage APC Worldwide Customer Support Page Warranty General Provisions