American Power Conversion MX28B200 RectFailComm, Min, Rect Cfg Alm, Rect CL Alm, Rect 1 CL

Page 40

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

PIN Entry

Screen for entry of the active password

PIN

m+

Security Level {0}

(PIN). Before any changes can be

 

0000

[PIN]

made, the correct pin for the desires

 

 

 

security level must be entered. Level 0 –

 

 

 

full read access. Level 1 –full read and

 

 

 

limited write access. Level 2 – full read

 

 

 

and write access.

 

 

Rectifier Communications Fail

The maximum rectifier communications

RectFailComm

m+

Timeout

response time allowed before a

1 min

Security Level {1}

communications failure is declared.

 

 

[MODULES/RECT/PARAM]

 

 

 

Rectifier Configuration Alarm

The output relay energized if the rectifier

Rect Cfg Alm

m+

Security Level {1}

configuration differs from its stored

Minor

[SYSTEM/SET-ALM]

configuration. This occurs if a rectifier is

 

 

 

added after configuration.

 

 

Rectifier Current Limit Alarm

The output relay that is energized or

Rect CL Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

[MODULES/RECT/SET-ALM]

occurs when a rectifier has been forced

 

 

 

into the current limited mode.

 

 

Rectifier Current Limit Alarm

The status will be “ON” if the rectifier has

Rect 1 CL

#

Status

been forced into its current limited mode.

OFF

{Status Only}

NOTE: This information can be

 

 

[MODULES/RECT/INFO]

viewed for each rectifier installed by

 

 

 

using the horizontal arrow keys.

 

 

Rectifier Current Output Status

A display of the DC output current for the

Rect 1 Curr

#

{Status Only}

individual rectifier. NOTE: This

24.9 A

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Description

Displays the model number of the

Rect 1 Desc

#

{Status Only}

installed rectifier. NOTE: This

MRF28H54

 

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Fail 1-of-N Alarm

The output relay energized if Rectifier

Rect 1ofN Almm+

Security Level {1}

Fail 1-of-N alarm occurs. This is a

Minor

[SYSTEM/SET-ALM]

special rectifier alarm group that signifies

 

 

 

that one rectifier has at least one alarm

 

 

 

condition.

 

 

Rectifier Fail 2-of-N Alarm

The output relay energized if Rectifier

Rect 2ofN Almm+

Security Level {1}

Fail 2-of-N alarm occurs This is a special

Major

[SYSTEM/SET-ALM]

rectifier alarm group that signifies that

 

 

 

more than one rectifier has at least one

 

 

 

alarm condition.

 

 

Rectifier Fail Safe Voltage

Rectifier default output voltage if

Rect Fail Safem+

Security Level {1}

communication with the control unit fails.

-54.00 V

[MODULES/RECT/PARAM]

 

 

 

Rectifier Fan Fail Alarm

The output relay that is energized or

Rect FF Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

[MODULES/RECT/SET-ALM]

occurs when a rectifier fan has failed.

 

 

Page 34

MX28B200/400 –48 VDC User’s Manual (990-9133)

Image 40
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionPage Safety First General PrecautionsPage Introduction General Information2 MX28B Block Diagram How to Use This Manual Page Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Power Connections VentilationPlanning the Battery installation Battery ConnectionsConnecting the Cables Battery Temperature Probe Installation DC System GroundingDC Power Output Over-Current Protection DC Circuit Breakers#10 studs on 5/8 centers DC GMT Fuses Fuse Rating Part NumberInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationGMT Fuse Installation Load ConnectionsCable Size Considerations Circuit Breaker Connections 1 to 50 AmpsCircuit Breaker Connections 60-100 Amps 1 Standard lug for 1 to 50A breakersGMT Fuse Connections 2 Adaptor and lugs for 60-100 Amp breakersRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Full System Power Up Technical Description OperationRectifier Management System Management System Output CapacitySystem Voltage Control System CurrentBattery Management System Status and Alarm ReportingBattery Charging and Protection DC DistributionControls and Indicators Battery Temperature CompensationBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Batt Disc Alm m+ MinorBatt Disc Thr m+ 10 aCir Bkr 48VCir Bkr 1 Alm m+ MajorFW Version 000189GMT 1 Alm GMT 8 AlmEnable LVD ResetIn-Rly 1 Alm IgnoreOEM S Offset Out-Rly 1 Alm m+Out-Rly 6 Alm m+ Out-RlyRectFailComm MinRect Cfg Alm Rect CL AlmDisable Rect 1 FFRect 1 RFA Rect RFA AlmSys LT Thr Sys LV AlmSys LV Thr 50.00SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysPage Command and Monitoring Protocol Remote MonitoringDescription Physical ConnectionsPage Specifications AC Input1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersRectifiers PscuPower Shelf Control Unit MechanicalMounting Environmental CompliancePage APC Worldwide Customer Support Page Warranty General Provisions