American Power Conversion MX28B200 Operation, Technical Description, Rectifier Management

Page 29

4 Operation

4.1. Technical Description

The MX28B-200/400 Power System is designed to supply safe –54 VDC primary power through the use of up to eight rectifier modules. In conjunction with an external battery string, it will supply backup power as well. The Power System Control Unit (PSCU) will monitor all MX28B functions and provides battery management including controlled battery recharge with temperature compensation and low voltage disconnect. Integrated DC output distribution supports loads ranging from ¼ Amp all the way to 100 Amp is available. Battery recharging, temperature compensation and low voltage disconnect are included. The controller can monitor up to 4 discrete external events with dry contact inputs.

4.2. Rectifier Management

AC Input Power

The basic component of the power system is the rectifier module, which rectifies utility AC into nominal 48 Volts DC. Each rectifier module requires 208/220/240V AC (MRF28H54BV), or 277V ac (MRF28H54BV50) single-phase, 50/60 Hz. A breaker installed in a remote panel should individually protect each rectifier circuit.

DC Output Power

The DC outputs of all the rectifiers in the system are connected to a common bus that is rated to carry the current of the entire system. The rectifier modules will equally share the entire load, independent of the PSCU. The rectifiers will continue to provide DC power if the PSCU is removed or fails.

Rectifier alarms reporting

The rectifier has numerous sensors inside the unit that monitor fan fail, high temperature, high/low voltage, etc. These rectifier sensors trigger outputs that are monitored by the PSCU. In addition rectifier current is measured inside each rectifier. The PSCU can trigger output relays in the event of a rectifier alarm. Refer to Section 4.6 for PSCU control functions.

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 23

Image 29
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsConnecting the Cables Battery ConnectionsPlanning the Battery installation DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesLoad Connections GMT Fuse InstallationCable Size Considerations Circuit Breaker Connections 1 to 50 Amps1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Smart Cable DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Rectifier Management OperationTechnical Description System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionBattery Temperature Compensation Controls and IndicatorsBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Minor Batt Disc Alm m+Batt Disc Thr m+ 10 a48V Cir BkrCir Bkr 1 Alm m+ Major000189 FW VersionGMT 1 Alm GMT 8 AlmLVD Reset EnableIn-Rly 1 Alm IgnoreOut-Rly 1 Alm m+ OEM S OffsetOut-Rly 6 Alm m+ Out-RlyMin RectFailCommRect Cfg Alm Rect CL AlmRect 1 FF DisableRect 1 RFA Rect RFA AlmSys LV Alm Sys LT ThrSys LV Thr 50.00Control Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsPage AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty