American Power Conversion MX28B200 FW Version, 000189, GMT 1 Alm, GMT 8 Alm, Hw Batt C Almm+

Page 37

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

Firmware Version

Version number of the control unit

FW Version

+

{Status Only}

firmware.

000189

[SYSTEM/SETUP]

NOTE: Actual firmware version

 

 

 

number displayed is the current

 

 

 

version as of the date of manufacture.

 

 

 

This parameter cannot be changed.

 

 

GMT 1 Alias

An alternate name (alias) that can be

GMT 1

m+

Security Level {1}

assigned to a GMT Fuse 1 if desired.

-48V

 

[MODULES/GMT/ALIAS]

 

 

 

 

 

 

GMT 8 Alias

An alternate name (alias) that can be

 

Security Level {1}

assigned to a GMT Fuse 8 if desired.

GMT 8

m+

[MODULES/GMT/ALIAS]

 

-48V

 

 

 

 

GMT 1 Blown

The Output Relay that is energized when

GMT 1 Alm

m+

Security Level {1}

GMT Fuse 1 is blown.

Major

[MODULES/GMT/SET-ALM]

 

 

 

 

 

 

GMT 8 Blown

The Output Relay that is energized when

 

Security Level {1}

GMT Fuse 8 is blown.

GMT 8 Alm

m+

[MODULES/GMT/SET-ALM]

 

Major

 

 

Hardware Battery Current

The output relay energized if there is a

Hw Batt C Almm+

Alarm

hardware failure in the battery current

Minor

Security Level {2}

monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware Battery Temperature

The output relay energized if there is a

Hw Batt T Almm+

Alarm

hardware failure in the battery

Minor

Security Level {2}

temperature monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware LVD Alarm

The output relay energized if there is a

Hw LVD Alm

m+

Security Level {2}

conflict between the commanded and

Minor

[SYSTEM/SET-ALM]

sensed positions of the LVD contactor.

 

 

 

Generally the contactor is open when it

 

 

 

should be closed.

 

 

Hardware System Temperature

The output relay energized if there is a

Hw Sys T Alm m+

Alarm

hardware failure in the system

Minor

Security Level {2}

temperature monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware System Voltage

The output relay energized if there is a

Hw Sys V Alm m+

Alarm

hardware failure in the system voltage

Minor

Security Level {2}

monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 31

Image 37
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsPlanning the Battery installation Battery ConnectionsConnecting the Cables DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesLoad Connections GMT Fuse InstallationCable Size Considerations Circuit Breaker Connections 1 to 50 Amps1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Smart Cable DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Technical Description OperationRectifier Management System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionBattery Temperature Compensation Controls and IndicatorsBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Minor Batt Disc Alm m+Batt Disc Thr m+ 10 a48V Cir BkrCir Bkr 1 Alm m+ Major000189 FW VersionGMT 1 Alm GMT 8 AlmLVD Reset EnableIn-Rly 1 Alm IgnoreOut-Rly 1 Alm m+ OEM S OffsetOut-Rly 6 Alm m+ Out-RlyMin RectFailCommRect Cfg Alm Rect CL AlmRect 1 FF DisableRect 1 RFA Rect RFA AlmSys LV Alm Sys LT ThrSys LV Thr 50.00Control Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsPage AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty