American Power Conversion MX28B200 In-Rly 1 Alm, Ignore, In-Rly 4 Alm, Input Relay, Lamp Test

Page 38

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

Input Relay 1

The Output Relay that is energized when

In-Rly 1 Alm

m+

Security Level {1}

an external contact closure or opening at

Ignore

[SYSTEM/IN-RLY/RLY-MAP]

the Input Relay 1 connection changes

 

 

state.

 

 

 

Input Relay 4

 

Security Level {1}

The Output Relay that is energized when

In-Rly 4 Alm

m+

[SYSTEM/IN-RLY/RLY-MAP]

an external contact closure or opening at

Ignore

 

the Input Relay 4 connection changes

 

 

 

 

state.

 

 

Input Relay 1 Alias

An alternate name (alias) can be

In-Rly 1

m+

Security Level {1}

assigned to Input Relay 1 if desired.

Input Relay 1

[SYSTEM/IN-RLY/ALIAS]

 

 

 

 

 

 

Input Relay 4 Alias

An alternate name (alias) can be

 

Security Level {1}

assigned to Input Relay 1 if desired

In-Rly 4

m+

[SYSTEM/IN-RLY/ALIAS]

 

Input Relay 4

 

 

Lamp Test

Setting Lamp Test to “ON” will turn on

Lamp Test

m+

Security Level {1}

the “MAJOR”, “MINOR”, “NORMAL”,

OFF

[SYSTEM/DIAG]

“MAJ”, and “MIN” LEDs on the control

 

 

 

unit front panel.

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an

LVD Option

m+

Security Level {1}

LVD. If the unit has an LVD, but it is

Enable

[MODULES/LVD/SET-ALM]

disabled, the controller will not

 

 

 

disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

-48.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

-42.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when

LVD Open Alm m+

Security Level {1}

the controller opens the LVD. If unit has

Minor

[MODULES/LVD/SET-ALM]

a battery LVD, no power will be available

 

 

 

to turn on any Output Relays.

 

 

Model Programming

Model type number for the MX28B DC

Model

m+

Security Level {2}

power plant

MX28B-200/400

[SYSTEM/SETUP]

NOTE: Changing the model number

 

 

 

causes the system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory

OEM R Gain

m+

Security Level {2}

calibration of system voltage

1.000 V

[OEM]

readings/settings.

 

 

OEM R Offset

Voltage offset adjustment for factory

OEM R Offset

m+

Security Level {2}

calibration of system voltage

0.000 V

[OEM]

readings/settings.

 

 

OEM S Gain

Current gain adjustment for factory

OEM S Gain

m+

Security Level {2}

calibration of battery current

1.000 A

[OEM]

readings/settings.

 

 

Page 32

MX28B200/400 –48 VDC User’s Manual (990-9133)

Image 38
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionPage Safety First General PrecautionsPage Introduction General Information2 MX28B Block Diagram How to Use This Manual Page Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationConnecting the Cables Battery ConnectionsPlanning the Battery installation Battery Temperature Probe Installation DC System GroundingDC Power Output Over-Current Protection DC Circuit Breakers#10 studs on 5/8 centers DC GMT Fuses Fuse Rating Part NumberInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationCable Size Considerations GMT Fuse InstallationLoad Connections Circuit Breaker Connections 1 to 50 AmpsCircuit Breaker Connections 60-100 Amps 1 Standard lug for 1 to 50A breakersGMT Fuse Connections 2 Adaptor and lugs for 60-100 Amp breakersFront Panel DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Smart Cable DB9 ConnectionExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Full System Power Up Rectifier Management OperationTechnical Description System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsBattery Temperature Compensation Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Batt Disc Thr m+ Batt Disc Alm m+Minor 10 aCir Bkr 1 Alm m+ Cir Bkr48V MajorGMT 1 Alm FW Version000189 GMT 8 AlmIn-Rly 1 Alm EnableLVD Reset IgnoreOut-Rly 6 Alm m+ OEM S OffsetOut-Rly 1 Alm m+ Out-RlyRect Cfg Alm RectFailCommMin Rect CL AlmRect 1 RFA DisableRect 1 FF Rect RFA AlmSys LV Thr Sys LT ThrSys LV Alm 50.00SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysPage Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsPage 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersRectifiers PscuPower Shelf Control Unit MechanicalMounting Environmental CompliancePage APC Worldwide Customer Support Page Warranty General Provisions