American Power Conversion MX28B200 Batt Disc Alm m+, Minor, Batt Disc Thr m+, 10 a, Batt Float

Page 35

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

Battery Discharge Alarm

The output relay energized if the battery

Batt Disc Alm m+

Security Level {1}

discharge current exceeds the

Minor

[BATT/SET-ALM]

programmed battery discharge threshold.

 

 

Battery Discharge Threshold

An alarm is generated if the battery

Batt Disc Thr m+

Security Level {1}

discharge current exceeds this value.

 

10 A

[BATT/SET-ALM]

 

 

 

Battery Float Voltage

One of three parameters that control the

Batt Float

m+

Security Level {1}

DC output voltage. Set the Float Voltage

-54.00 V

[BATT/PARAM]

at 25°C battery temperature per the

 

 

 

battery manufacturers recommendations.

 

 

Battery High Temperature

The output relay energized if the battery

Batt HT Alm

m+

Alarm

temperature exceeds the Battery High

Minor

Security Level {1}

Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery High Temperature

Battery Temperature is temperature

Batt HT Thr

m+

Threshold

measured at the battery probe. An alarm

70.0 C

Security Level {1}

is generated if the battery temperature

 

 

[BATT/SET-ALM]

exceeds this value.

 

 

Battery High Voltage Alarm

The output relay energized if the DC

Batt HV Alm

m+

Security Level {1}

output voltage rises above the battery

Minor

[BATT/SET-ALM]

high voltage threshold.

 

 

Battery High Voltage Threshold

An alarm will be reported if temperature

Batt HV Thr

m+

Security Level {1}

is lower than the temperature entered.

-58.00 V

[BATT/SET-ALM]

An alarm is generated if the DC output

 

 

 

voltage rises above this value.

 

 

Battery Low Temperature

The output relay energized if the Battery

Batt LT Alm

m+

Alarm

Temperature drops below the battery

Minor

Security Level {1}

Low Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery Low Temperature

Battery Temperature is temperature

Batt LT Thr

m+

Threshold Security Level {1}

measured at the battery probe. An alarm

 

0.0 C

[BATT/SET-ALM]

is generated if the battery temperature

 

 

 

drops below this value.

 

 

Battery Low Voltage Alarm

The output relay energized if the DC

Batt LV Alm

m+

Security Level {1}

output voltage drops below the battery

Minor

[BATT/SET-ALM]

low voltage threshold.

 

 

Battery Low Voltage Threshold

An alarm is generated if the DC output

Batt LV Thr

m+

Security Level {1}

voltage drops below this value.

-44.00 V

[BATT/SET-ALM]

 

 

 

Battery Maximum Recharge

One of three parameters that control the

Batt Max Rechm+

Current

DC output voltage. If Battery Current

 

12 A

Security Level {1}

surpasses the Maximum Battery

 

 

[BATT/PARAM]

Recharge Current, the DC output voltage

 

 

 

will be reduced (the system limits the

 

 

 

charging current to this programmable

 

 

 

value).

 

 

Battery Temperature

Battery temperature measured by the

Batt Temp

+

{Status Only}

system controller at the optional battery

25.2 C

[STATUS]

temperature sensor probe.

 

 

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 29

Image 35
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsConnecting the Cables Battery ConnectionsPlanning the Battery installation DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesCircuit Breaker Connections 1 to 50 Amps GMT Fuse InstallationLoad Connections Cable Size Considerations1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsSmart Cable DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Rectifier Management OperationTechnical Description System Current System ManagementSystem Output Capacity System Voltage ControlDC Distribution Battery ManagementSystem Status and Alarm Reporting Battery Charging and ProtectionFront Panel User Interface Controls and IndicatorsBattery Temperature Compensation Battery/Load Low Voltage DisconnectMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values 10 a Batt Disc Alm m+Minor Batt Disc Thr m+Major Cir Bkr48V Cir Bkr 1 Alm m+GMT 8 Alm FW Version000189 GMT 1 AlmIgnore EnableLVD Reset In-Rly 1 AlmOut-Rly OEM S OffsetOut-Rly 1 Alm m+ Out-Rly 6 Alm m+Rect CL Alm RectFailCommMin Rect Cfg AlmRect RFA Alm DisableRect 1 FF Rect 1 RFA50.00 Sys LT ThrSys LV Alm Sys LV ThrControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Physical Connections Command and Monitoring ProtocolRemote Monitoring DescriptionPage 1MRF28H54BV50 Rectifiers SpecificationsAC Input 1MRF28H54BV RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty