4.7. Alarm Outputs (Output Relays)

There are eight alarm output relays designated Relay 1 through Relay 6, Minor, and Major, respectively. Various system parameters may be programmed to activate any of these alarm relays when set thresholds are exceeded or specific conditions occur. The first six relays can also be assigned a priority and routed or “mapped” to other output alarm relays. Available assignments are “Ignore”, “Major”, “Minor”, and “Relay 1” ···

“Relay 6”. Screens for making these assignments are located at [SYSTEM/OUT- RLY/RLY-MAP]. This feature makes it possible for a single alarm condition to activate multiple alarm output relays including the Minor or Major alarm relay. A user defined name or “alias” may also be assigned to each of the eight output relay alarms. Screens for making these assignments are located at [SYSTEM/OUT-RLY/ALIAS]. For information on making wiring connections to the alarm output relays refer to Section 3.9

4.8. External Alarm Inputs (Input Relays)

The controller can monitor any external device that uses a switch or relay to output status information. Connecting the external device to the input relay connections is the first step. The four external alarm inputs (also referred to as “Input Relay Alarms”) can be assigned a priority and routed or “mapped” to alarm output relays. Available assignments are “Ignore”, “Major”, “Minor”, and “Relay 1” ··· “Relay 6” (do not map relay to itself or the alarm will never clear). Screens for making the assignments are located at [SYSTEM/IN- RLY/RLY-MAP]. A user defined name or “alias” may also be assigned to each of these input alarms. Screens for making these assignments are located at [SYSTEM/IN- RLY/ALIAS]. For information on wiring connections to these inputs refer to Section 3.10

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 43

Image 49
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsPlanning the Battery installation Battery ConnectionsConnecting the Cables DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesLoad Connections GMT Fuse InstallationCable Size Considerations Circuit Breaker Connections 1 to 50 Amps1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Smart Cable DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Technical Description OperationRectifier Management System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionBattery Temperature Compensation Controls and IndicatorsBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Minor Batt Disc Alm m+Batt Disc Thr m+ 10 a48V Cir BkrCir Bkr 1 Alm m+ Major000189 FW VersionGMT 1 Alm GMT 8 AlmLVD Reset EnableIn-Rly 1 Alm IgnoreOut-Rly 1 Alm m+ OEM S OffsetOut-Rly 6 Alm m+ Out-RlyMin RectFailCommRect Cfg Alm Rect CL AlmRect 1 FF DisableRect 1 RFA Rect RFA AlmSys LV Alm Sys LT ThrSys LV Thr 50.00Control Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsPage AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty