American Power Conversion MX28B200 user manual Specifications, AC Input, 1MRF28H54BV Rectifiers

Page 53

6 Specifications

The overall system specifications can vary, depending upon the number of rectifier modules. Note that some specification items are provided on a “per rectifier” basis and must be combined or totaled for a give system configuration.

6.1. AC Input

1MRF28H54BV Rectifiers

Nominal Input Voltage

208, 230 VAC

 

 

Input Voltage Range

176 – 264 VAC

 

 

AC Frequency Range

45 – 65 Hz

 

 

Apparent Power Factor

99% Typical, 98% Minimum

 

 

Maximum Input Current (per Rectifier)

13.9 Amps @ 230V AC

 

 

1MRF28H54BV50 Rectifiers

 

 

 

Nominal Input Voltage

277 VAC

 

 

Input Voltage Range

195 – 264 VAC

 

 

AC Frequency Range

45 – 65 Hz

 

 

Apparent Power Factor

99% Typical, 98% Minimum

 

 

Maximum Input Current (per Rectifier)

11.0 Amps @ 277V AC

 

 

6.2.DC Output (with either 1MRF28H54BV Rectifiers and 1MRF28H54BV50 Rectifiers)

Nominal Output Voltage (factory set)

54.5 VDC (**)

 

 

Operating Voltage Range

44 – 58 VDC (**)

 

 

Rated Output Current (per Rectifier)

50 A

 

 

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 47

Image 53
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsConnecting the Cables Battery ConnectionsPlanning the Battery installation DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesLoad Connections GMT Fuse InstallationCable Size Considerations Circuit Breaker Connections 1 to 50 Amps1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Smart Cable DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Rectifier Management OperationTechnical Description System Output Capacity System ManagementSystem Voltage Control System CurrentSystem Status and Alarm Reporting Battery ManagementBattery Charging and Protection DC DistributionBattery Temperature Compensation Controls and IndicatorsBattery/Load Low Voltage Disconnect Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Minor Batt Disc Alm m+Batt Disc Thr m+ 10 a48V Cir BkrCir Bkr 1 Alm m+ Major000189 FW VersionGMT 1 Alm GMT 8 AlmLVD Reset EnableIn-Rly 1 Alm IgnoreOut-Rly 1 Alm m+ OEM S OffsetOut-Rly 6 Alm m+ Out-RlyMin RectFailCommRect Cfg Alm Rect CL AlmRect 1 FF DisableRect 1 RFA Rect RFA AlmSys LV Alm Sys LT ThrSys LV Thr 50.00Control Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Remote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsPage AC Input Specifications1MRF28H54BV Rectifiers 1MRF28H54BV50 RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty