American Power Conversion MX28B200 Sys LT Thr, Sys LV Alm, Sys LV Thr, 50.00, Sys Temp, 26.7 C

Page 42

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

System Low Temperature

System Temperature is ambient

Sys LT Thr

m+

Threshold

temperature measured inside the

0.0 C

Security Level {1}

controller. An alarm will be reported if

 

 

[SYSTEM/SET-ALM]

temperature is lower than the

 

 

 

temperature entered.

 

 

System Low Voltage Alarm

The output relay energized if the System

Sys LV Alm

m+

Security Level {1}

Voltage is below the System Low Voltage

Minor

[SYSTEM/SET-ALM]

threshold.

 

 

System Low Voltage Threshold

System Voltage is bus voltage measured

Sys LV Thr

m+

Security Level {1}

by the controller. An alarm will be

-50.00 V

[SYSTEM/SET-ALM]

reported if voltage is lower than the

 

 

 

voltage entered.

 

 

System Temperature

System temperature measured within the

Sys Temp

+

{Status Only}

control unit.

26.7 C

[STATUS]

 

 

 

System Voltage

System output voltage measured

Sys Voltage

+

{Status Only}

between the MX28B DC power plant -

-54.00 V

[STATUS]

48V and return buses.

 

 

Test Major Relay

Setting this parameter to “ON” de-

Test Maj Rly

m+

Security Level {1}

energizes the Major Relay and turns on

OFF

[SYSTEM/DIAG]

the “MAJ” LED on the control unit front

 

 

 

panel. In normal operation Major Relay

 

 

 

is energized so that when a loss of –48

 

 

 

VDC power occurs, the relay will change

 

 

 

state.

 

 

Test Minor Relay

Setting this parameter to “ON” energizes

Test Min Rly

m+

Security Level {1}

the Minor Relay and turns on the “MIN”

OFF

[SYSTEM/DIAG]

LED on the control unit front panel.

 

 

Test Relay 1

Setting this parameter to “ON” energizes

Test Relay 1

m+

Security Level {1}

Relay 1 and turns on the “ALM1” LED on

OFF

[SYSTEM/DIAG]

the control unit front panel.

 

 

 

 

 

Test Relay 6

Setting this parameter to “ON” energizes

 

Security Level {1}

Relay 6 and turns on the “ALM6” LED on

Test Relay 6

m+

[SYSTEM/DIAG]

the control unit front panel.

OFF

 

 

 

 

 

Test Relay Enable

This parameter must be set to “Enable”

Test Relay En m+

Security Level {1}

to permit the eight output relays to be

Disable

[SYSTEM/DIAG]

manually tested; otherwise, the state of

 

 

 

the relays will be per system conditions.

 

 

Time

Internal system clock time (24-hour

Time

m+

Security Level {1}

format). Used as a date stamp in the

9:00:25

[SYSTEM/DATE]

event log.

 

 

Page 36

MX28B200/400 –48 VDC User’s Manual (990-9133)

Image 42
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionPage Safety First General PrecautionsPage Introduction General Information2 MX28B Block Diagram How to Use This Manual Page Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation DC System GroundingDC Power Output Over-Current Protection DC Circuit Breakers#10 studs on 5/8 centers DC GMT Fuses Fuse Rating Part NumberInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationCable Size Considerations GMT Fuse InstallationLoad Connections Circuit Breaker Connections 1 to 50 AmpsCircuit Breaker Connections 60-100 Amps 1 Standard lug for 1 to 50A breakersGMT Fuse Connections 2 Adaptor and lugs for 60-100 Amp breakersFront Panel DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Smart Cable DB9 ConnectionExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Full System Power Up Operation Technical DescriptionRectifier Management System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsBattery Temperature Compensation Front Panel User InterfaceMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values Batt Disc Thr m+ Batt Disc Alm m+Minor 10 aCir Bkr 1 Alm m+ Cir Bkr48V MajorGMT 1 Alm FW Version000189 GMT 8 AlmIn-Rly 1 Alm EnableLVD Reset IgnoreOut-Rly 6 Alm m+ OEM S OffsetOut-Rly 1 Alm m+ Out-RlyRect Cfg Alm RectFailCommMin Rect CL AlmRect 1 RFA DisableRect 1 FF Rect RFA AlmSys LV Thr Sys LT ThrSys LV Alm 50.00SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysPage Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsPage 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersRectifiers PscuPower Shelf Control Unit MechanicalMounting Environmental CompliancePage APC Worldwide Customer Support Page Warranty General Provisions