American Power Conversion MX28B200 user manual System Parameters Verification/Adjustment

Page 27

3)Verify that all rectifiers have been installed.

4)Apply AC Power. Turn on the circuit breakers that supply ac power to the rectifiers in the MX28B DC power plant. The main screen should appear on the control unit display (see Figure 4.6-1). The display on the control unit is a 2-lines by 16- characters display. The cursor cycles below the characters of the active selection on the display. Information shown in the second line of Figure 4.6-1 that extends beyond 16 characters (to the right of the “S” in “ALARMS”) can viewed on the control unit display by using the scrolling controls (refer to Section 4.6 for operation of the control unit).

NOTE: When AC power is initially applied, there is a 60-second period during which no alarms are reported.

WARNING: The DC power plant is supplied from a nominal 220VAC, 50/60 Hz source. Keep the AC input enclosure cover in place when the system is operational or energized

.

3.13.System Parameters Verification/Adjustment

The MX28B system control unit is delivered with pre-programmed parameter default settings. A complete listing and description of all system configuration parameters as well as displayable system status and information is provided in Section 4.6. Read Section 4.1 to gain an understanding of and how to use the operational features provided by the MX28B DC power plant. As a minimum, the following parameters should be verified and adjusted, if required, before connecting batteries or loads to the power plant:

1)Battery Float Voltage - default = -54.00V DC (Check the manufacturer’s recommendation for the batteries being used in the system.)

2)Battery Maximum Recharge Rate - default = 12A. (Bellcore specifications recommend a maximum charging rate of capacity (in Ampere-hours) divided by 20 hours; check the manufacturer’s recommendation.)

3)System Voltage - measurement -54.00V DC (This is a measurement by the system of the DC output bus voltage.)

4)LVD Option - default = “Enable” (If the MX28B does not have an LVD installed, this should be changed to “Disable”.)

5)Rectifier Information - Check the rectifier information displays to verify that all rectifiers installed can be viewed on the control unit display and that no rectifier alarms are active.

Section 4.6 provides location information for these parameters and how to make changes if required.

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 21

Image 27
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsBattery Connections Planning the Battery installationConnecting the Cables DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesCircuit Breaker Connections 1 to 50 Amps GMT Fuse InstallationLoad Connections Cable Size Considerations1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsSmart Cable DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Operation Technical DescriptionRectifier Management System Current System ManagementSystem Output Capacity System Voltage ControlDC Distribution Battery ManagementSystem Status and Alarm Reporting Battery Charging and ProtectionFront Panel User Interface Controls and IndicatorsBattery Temperature Compensation Battery/Load Low Voltage DisconnectMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values 10 a Batt Disc Alm m+Minor Batt Disc Thr m+Major Cir Bkr48V Cir Bkr 1 Alm m+GMT 8 Alm FW Version000189 GMT 1 AlmIgnore EnableLVD Reset In-Rly 1 AlmOut-Rly OEM S OffsetOut-Rly 1 Alm m+ Out-Rly 6 Alm m+Rect CL Alm RectFailCommMin Rect Cfg AlmRect RFA Alm DisableRect 1 FF Rect 1 RFA50.00 Sys LT ThrSys LV Alm Sys LV ThrControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Physical Connections Command and Monitoring ProtocolRemote Monitoring DescriptionPage 1MRF28H54BV50 Rectifiers SpecificationsAC Input 1MRF28H54BV RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty