PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

OEM S Offset

Current offset adjustment for factory

OEM S Offset

m+

Security Level {2}

calibration of battery current

0.0 A

[OEM]

readings/settings.

 

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped”

Out-Rly 1 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

MAP]

 

 

 

 

 

Output Relay 6 Alarm

Output Relay 6 Alarm can be “mapped”

Out-Rly 6 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

MAP]

 

 

 

Output Relay 1 Alias

An alternate name (alias) can be

Out-Rly 1

m+

Security Level {1}

assigned to Output Relay 1 if desired.

Relay 1

 

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

 

An alternate name (alias) can be

m+

Output Relay 6 Alias {1}

assigned to Output Relay 6 if desired.

Out-Rly 6

[SYSTEM/OUT-RLY/ALIAS]

 

Relay 6

 

Output Relay 1 Delay

Delay between sensing of the alarm

Out-Rly 1 Dly m+

Security Level {1}

condition and activation of Output Relay

0 sec

[SYSTEM/OUT-RLY/RLY-

1. An alarm condition must exist for

 

 

MAP]

longer than the delay to be activated.

 

 

 

Delay between sensing of the alarm

 

Output Relay 6 Delay

condition and activation of Output Relay

Out-Rly 6 Dly m+

Security Level {1}

6. An alarm condition must exist for

0 sec

[SYSTEM/OUT-RLY/RLY-

longer than the delay to be activated.

 

 

MAP]

 

 

 

Output Relay Major Alias

An alternate name (alias) can be

Relay Major

 

Security Level {1}

assigned to the major Relay if desired.

m+

 

[SYSTEM/OUT-RLY/ALIAS]

 

Major

 

 

 

 

Output Relay Minor Alias

An alternate name (alias) can be

Relay Minor

 

Security Level {1}

assigned to the Minor Relay if desired.

m+

 

[SYSTEM/OUT-RLY/ALIAS]

 

Minor

 

 

PIN 1 change

Permanently change password (PIN) that

PIN

m+

Security Level {2}

permits security Level 1 parameter

 

 

[SYSTEM/SETUP]

changes - limited access.

1111

 

 

 

 

PIN 2 Change

Permanently change password (PIN) that

PIN 2

m+

Security Level {2}

permits security Level 2 parameter

 

 

[SYSTEM/SETUP]

changes - unlimited access.

2222

 

 

 

 

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 33

Image 39
Contents VDC Power Systems Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryPage General Precautions Safety FirstPage General Information Introduction2 MX28B Block Diagram How to Use This Manual Page Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsBattery Connections Planning the Battery installationConnecting the Cables DC System Grounding Battery Temperature Probe InstallationDC Circuit Breakers DC Power Output Over-Current Protection#10 studs on 5/8 centers Fuse Rating Part Number DC GMT FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and FusesCircuit Breaker Connections 1 to 50 Amps GMT Fuse InstallationLoad Connections Cable Size Considerations1 Standard lug for 1 to 50A breakers Circuit Breaker Connections 60-100 Amps2 Adaptor and lugs for 60-100 Amp breakers GMT Fuse ConnectionsSmart Cable DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationSystem Parameters Verification/Adjustment Full System Power Up Operation Technical DescriptionRectifier Management System Current System ManagementSystem Output Capacity System Voltage ControlDC Distribution Battery ManagementSystem Status and Alarm Reporting Battery Charging and ProtectionFront Panel User Interface Controls and IndicatorsBattery Temperature Compensation Battery/Load Low Voltage DisconnectMX28B Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default Values 10 a Batt Disc Alm m+Minor Batt Disc Thr m+Major Cir Bkr48V Cir Bkr 1 Alm m+GMT 8 Alm FW Version000189 GMT 1 AlmIgnore EnableLVD Reset In-Rly 1 AlmOut-Rly OEM S OffsetOut-Rly 1 Alm m+ Out-Rly 6 Alm m+Rect CL Alm RectFailCommMin Rect Cfg AlmRect RFA Alm DisableRect 1 FF Rect 1 RFA50.00 Sys LT ThrSys LV Alm Sys LV ThrControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin AM Info Modgmt LM Alias GMT MOD Modlvd Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPage Physical Connections Command and Monitoring ProtocolRemote Monitoring DescriptionPage 1MRF28H54BV50 Rectifiers SpecificationsAC Input 1MRF28H54BV RectifiersPscu RectifiersMechanical Power Shelf Control UnitMounting Compliance EnvironmentalPage APC Worldwide Customer Support Page General Provisions Warranty