American Power Conversion PD80KF6FK1-M manual How to connect contacts to the PDU monitoring unit

Page 28

PDU Display Interface

How to connect contacts to the PDU monitoring unit

1.Choose one or more contact number on the User/EPO contacts port on the user connection plate to which you will connect the contacts. The user connection plate is connected to the PDU monitoring unit.

2.From the PDU display interface:

a.Press the ESC or ENTER key to go to the top-level menu screen.

b.Select Contacts on the top-level menu screen, and press the ENTER key.

Load-Meter

Alarms

Volt-Meter

Panel

Contacts

Config

Breakers

Help

c.Select Contact Inputs (or Relay Outputs) and press ENTER to display the contact inputs (or relay outputs) screen.

>Contact Inputs

>Relay Outputs

>Alarm Relay Map

d. Select Contact In and press the ENTER key to select the number of the contact you are connecting. The continue arrow will appear next to the contact number.

Contact In:01of04

Name:User Contact 1

Normal: Open

Status: Closed

e. Press the Up or Down arrow key to select the appropriate contact number, and press the

ENTER key.

f.Press the Down arrow key to enter a unique Name for the contact and to configure the Normal state of the contact (Open or Closed). The default Normal state is Open. Press the ENTER key to select the item to configure.

You will be prompted for your password to configure these items.

Note

3.Connect contact wires (300V-rated cabling required) to the User Contacts terminal block on the user connection plate. You will need a 2.5-mm standard screwdriver.

4.Run the wires from the terminal block out the roof or under the floor of the PDU to your contact’s location.

Ensure that wires are properly retained and away from high voltage lines and breakers.

Warning

20

80kW InfraStruXure PDU—Operation and Configuration

Image 28
Contents 80kW InfraStruXure PDU Page How to find updates to this manual About This ManualAudience Companion manualsPage Contents System Operation Specifications Product Information Safety Safety symbols used in this manualCross-reference symbols used in this manual OverviewInstallation/Maintenance Maintenance performed while the PDU is receiving input powerTotal Power Off Emergency Power Off EPOEMI Overview InfraStruXure PDU ComponentsPDU front view exterior Front view interior  Wraparound Maintenance bypass Panel- Front view door openRear view interior PDU monitoring unit User connection plate  Page PDU Display Interface       Top-level menu screen Top-level status screensNavigating through screens Password-protected screens Power Factor Load-Meter ScreenVolt-Meter Screen Contacts Screen OverviewInput Contacts Open or ClosedPDU Display Interface How to connect contacts to the PDU monitoring unit Breakers Screen Main InputBypass Input Cross TieAlarms Screen New Logged ItemsEntire Log Clear LogAlarm Setup Alarm BeeperLoading Limits Voltage LimitsPDU Alarms Alarm Condition Explanation Message When Condition ClearedBranch Ckt Loading Panel ScreenBranch Ckt Limits Panel Configuration Distribution panelGlobal Panel Config Config Screen System PasswordSystem/Network Date/TimeInput Config Electrical ConfigOutput Config Factory Defaults Firmware UpdatesManufacturer Data System IDHow to Transfer the UPS into Maintenance Bypass Operation System OperationSystem Operation System Operation How to Return from Maintenance Bypass Operation Confirm Yes, UPS Load on No, Abort Confirm Yes, UPS into Bypass No, Abort How to Ensure Total Power Off Set the UPS System Enable switch to the OFF positionSystem Operation How to Apply Power to the System PowerView RM Rev 000 English Please wait Top-Level Status Screen System Operation Communication Configuration InfraStruXure PDU Management OptionsInfraStruXure Manager Network management interfacesConfiguring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure ManagerConfiguration Overview Configuring the Network Management InterfaceConnect the InfraStruXure PDU to your network TCP/IP configuration methods Device IP Configuration WizardBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where Use apc for the User Name and Password Local access to the control consoleRemote access to the control console Control console Use apc for both User Name and PasswordChoose Network from the Control Console menu Web interface Snmp FTP and SCP 80kW InfraStruXure PDU-Operation and Configuration Important Safety Instructions Customizing and Updating the PDUPDU Orderable Part List Power CablesCircuit Breakers 30A, 3-wire power cables Add a power cable to the PDU or RDP How to Add Circuit Breakers and Power CablesAdd a circuit breaker on the PDU Customizing and Updating the PDU How to Test the EPO Switch Testing the EPO wiring and switchesSafety warnings Customizing and Updating the PDU ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit Downloading firmware upgrades from a local computer How to Download Firmware UpgradesUpgrading the PDU monitor processor Xmodem Specifications 80kW InfraStruXure PDUPD80F6FK1-M PD80G6FK1-M PD80L6FK1-M PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M Page InfraStruXure Standard Warranty Product InformationProduct Information APC Three-Phase Systems Life-Support PolicyHow to Obtain Service How to contact APCAppendix Changes in This ManualGeneral Changes Changes by page numberPage Index 80kW InfraStruXure PDU-Operation and Configuration UPS Page Page Page Page APC Worldwide Customer Support