System Operation
c.Select UPS Into Bypass on the Control menu, and press the ENTER key.
d.Confirm the selection on the next screen: select Yes, UPS into Bypass, and press the ENTER key.
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirmation Screen
Confirm
Yes, UPS into Bypass No, Abort
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate the Q2 circuit breaker.
Note
7. Close (turn ON) the Q2 circuit breaker on the PDU.
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to operate the Q3 circuit breaker
Note
8. Open (turn OFF) the Q3 circuit breaker on the PDU.
The UPS automatically comes out of Static Bypass operation.
36 | 80kW InfraStruXure |