American Power Conversion PD80KG6FK1-M, PD80KF6FK1-M, PD80KL6FK1-M manual System Operation

Page 6

Contacts Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Breakers Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Alarm/Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Alarm Beeper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

PDU Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Panel Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Branch Ckt Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Branch Ckt Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Panel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Global Panel Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Config Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

System/Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Electrical Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Manufacturer Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

System ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Firmware Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

System Operation

31

How to Transfer the UPS into Maintenance Bypass Operation . 31 How to Return from Maintenance Bypass Operation . . . . . . . . 34 How to Ensure Total Power Off . . . . . . . . . . . . . . . . . . . . . . . 37 How to Apply Power to the System . . . . . . . . . . . . . . . . . . . . . 39

Communication Configuration

43

InfraStruXure PDU Management Options . . . . . . . . . . . . . . . . . 43

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

InfraStruXure Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Network management interfaces . . . . . . . . . . . . . . . . . . . . 43

Configuring the InfraStruXure Manager . . . . . . . . . . . . . . . . . . 44

iv

80kW InfraStruXure PDU—Operation and Configuration

Image 6
Contents 80kW InfraStruXure PDU Page Audience How to find updates to this manualAbout This Manual Companion manualsPage Contents System Operation Specifications Product Information Cross-reference symbols used in this manual SafetySafety symbols used in this manual OverviewInstallation/Maintenance Maintenance performed while the PDU is receiving input powerTotal Power Off Emergency Power Off EPOEMI Overview InfraStruXure PDU ComponentsPDU front view exterior Front view interior  Wraparound Maintenance bypass Panel- Front view door openRear view interior PDU monitoring unit User connection plate  Page PDU Display Interface       Top-level status screens Top-level menu screenNavigating through screens Password-protected screens Power Factor Load-Meter ScreenVolt-Meter Screen Input Contacts Contacts ScreenOverview Open or ClosedPDU Display Interface How to connect contacts to the PDU monitoring unit Bypass Input Breakers ScreenMain Input Cross TieEntire Log Alarms ScreenNew Logged Items Clear LogLoading Limits Alarm SetupAlarm Beeper Voltage LimitsPDU Alarms Alarm Condition Explanation Message When Condition ClearedPanel Screen Branch Ckt LoadingBranch Ckt Limits Panel Configuration Distribution panelGlobal Panel Config System/Network Config ScreenSystem Password Date/TimeElectrical Config Input ConfigOutput Config Manufacturer Data Factory DefaultsFirmware Updates System IDHow to Transfer the UPS into Maintenance Bypass Operation System OperationSystem Operation System Operation How to Return from Maintenance Bypass Operation Confirm Yes, UPS Load on No, Abort Confirm Yes, UPS into Bypass No, Abort How to Ensure Total Power Off Set the UPS System Enable switch to the OFF positionSystem Operation How to Apply Power to the System PowerView RM Rev 000 English Please wait Top-Level Status Screen System Operation InfraStruXure Manager Communication ConfigurationInfraStruXure PDU Management Options Network management interfacesConfiguring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure ManagerConfiguring the Network Management Interface Configuration OverviewConnect the InfraStruXure PDU to your network TCP/IP configuration methods Device IP Configuration WizardBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where Local access to the control console Use apc for the User Name and PasswordRemote access to the control console Use apc for both User Name and Password Control consoleChoose Network from the Control Console menu Web interface Snmp FTP and SCP 80kW InfraStruXure PDU-Operation and Configuration Important Safety Instructions Customizing and Updating the PDUPower Cables PDU Orderable Part ListCircuit Breakers 30A, 3-wire power cables How to Add Circuit Breakers and Power Cables Add a power cable to the PDU or RDPAdd a circuit breaker on the PDU Customizing and Updating the PDU How to Test the EPO Switch Testing the EPO wiring and switchesSafety warnings Customizing and Updating the PDU ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit How to Download Firmware Upgrades Downloading firmware upgrades from a local computerUpgrading the PDU monitor processor Xmodem Specifications 80kW InfraStruXure PDUPD80F6FK1-M PD80G6FK1-M PD80L6FK1-M PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M Page InfraStruXure Standard Warranty Product InformationProduct Information APC Three-Phase Systems Life-Support PolicyHow to Obtain Service How to contact APCGeneral Changes AppendixChanges in This Manual Changes by page numberPage Index 80kW InfraStruXure PDU-Operation and Configuration UPS Page Page Page Page APC Worldwide Customer Support