4.Close (turn ON) the UPS System Enable switch.
The UPS will show a Forced Bypass message on the display interface, and the Fault LED will be red.
5.Command the UPS to apply power to the load:
a.Press the ESC key at the
b.Select Control, and press the ENTER key.
c.Select Turn Load On from the Control menu, and press the ENTER key.
System Operation
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
d.On the next screen: select Yes, UPS Load ON, and press the ENTER key.
Confirmation Screen
Confirm
![](/images/new-backgrounds/1184164/18416485xi4.webp)
Yes, UPS Load ON
No, Abort
The Load On LED illuminates and the interface displays the following two screens:
UPS has been
commanded to turn load power on...
UPS load is on
Press any key...
6. Command the UPS into static bypass operation through the UPS display interface:
a.Press the ESC key at the
b.Select Control on the
ENTER key.
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
80kW InfraStruXure | 35 |