PDU Display Interface
Alarm Setup
Use this option of the Alarms screen to access the following options:
Loading Limits | Configure the following in amps and as a percentage of full load: | |
| • | Out High: The upper limit for output current |
| • | Out Low: The lower limit for output current |
| • | Out Neut: The upper limit for current on the neutral wire for |
|
| the output phases |
Voltage Limits | Configure the following as a percentage under or over the rated | |
| voltage: | |
| • Input: The allowed range for input voltage | |
| • Output: The allowed range for output voltage | |
| • Bypass: The allowed range for bypass input voltage (only on | |
|
| PDUs with |
Other Limits | Configure these limits: |
Frequency: The frequency variation, in hertz, that is acceptable for the output current.
Global Alarm Config Set all the loading limits or all the voltage limits simultaneously as a percentage of full load:
•Load Limits: Set the same percentage for the upper limit for output current, the lower limit for output current, and the upper limit for current on the neutral wire for the output phases. (Use the Loading Limits option to set these thresholds individually).
•Volt Limits: Set the same percentage for the high and low thresholds for input and output voltage. (Use the Voltage Limits option to set these thresholds individually).
Select Apply Now and then YES to implement your changes.
Alarm Beeper
Use this option of the Alarms screen to turn the alarm beeper ON or OFF.
80kW InfraStruXure | 23 |