7.Read the messages displayed on the UPS display interface:
a.Note any alarms, and verify that they are appropriate for
b.Verify that the UPS accepts the input.
8.Command the UPS to apply power to the load:
a.Press the ESC key at the
b.Select Control, and press the ENTER key.
System Operation
Top-Level Status Screen
Fuel%
Load%
In 208V out000V 60Hz
Runtime: 1hr 2m
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
c.Select Turn Load On from the Control menu, and press the ENTER key.
d.On the next screen: select Yes, UPS Load ON, and press the ENTER key.
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirmation Screen
Confirm
Yes, UPS Load ON
No, Abort
The Load On LED illuminates, and the interface displays the following two screens:
UPS has been
commanded to turn load power on...
UPS load is on
Press any key...
80kW InfraStruXure | 41 |