American Power Conversion PD80KL6FK1-M, PD80KG6FK1-M, PD80KF6FK1-M manual

Page 89
Image 89
Contents 80kW InfraStruXure PDU Page About This Manual How to find updates to this manualAudience Companion manualsPage Contents System Operation Specifications Product Information Safety symbols used in this manual SafetyCross-reference symbols used in this manual OverviewMaintenance performed while the PDU is receiving input power Installation/MaintenanceEmergency Power Off EPO Total Power OffEMI InfraStruXure PDU Components OverviewPDU front view exterior Front view interior Front view door open  Wraparound Maintenance bypass Panel-Rear view interior PDU monitoring unit   User connection platePage        PDU Display InterfaceNavigating through screens Top-level status screensTop-level menu screen Password-protected screens Load-Meter Screen Power FactorVolt-Meter Screen Overview Contacts ScreenInput Contacts Open or ClosedPDU Display Interface How to connect contacts to the PDU monitoring unit Main Input Breakers ScreenBypass Input Cross TieNew Logged Items Alarms ScreenEntire Log Clear LogAlarm Beeper Alarm SetupLoading Limits Voltage LimitsAlarm Condition Explanation Message When Condition Cleared PDU AlarmsBranch Ckt Limits Panel ScreenBranch Ckt Loading Distribution panel Panel ConfigurationGlobal Panel Config System Password Config ScreenSystem/Network Date/TimeOutput Config Electrical ConfigInput Config Firmware Updates Factory DefaultsManufacturer Data System IDSystem Operation How to Transfer the UPS into Maintenance Bypass OperationSystem Operation System Operation How to Return from Maintenance Bypass Operation Confirm Yes, UPS Load on No, Abort Confirm Yes, UPS into Bypass No, Abort Set the UPS System Enable switch to the OFF position How to Ensure Total Power OffSystem Operation How to Apply Power to the System PowerView RM Rev 000 English Please wait Top-Level Status Screen System Operation InfraStruXure PDU Management Options Communication ConfigurationInfraStruXure Manager Network management interfacesConnect the InfraStruXure PDU to the InfraStruXure Manager Configuring the InfraStruXure ManagerConnect the InfraStruXure PDU to your network Configuring the Network Management InterfaceConfiguration Overview Device IP Configuration Wizard TCP/IP configuration methodsBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where Remote access to the control console Local access to the control consoleUse apc for the User Name and Password Choose Network from the Control Console menu Use apc for both User Name and PasswordControl console Web interface Snmp FTP and SCP 80kW InfraStruXure PDU-Operation and Configuration Customizing and Updating the PDU Important Safety InstructionsCircuit Breakers Power CablesPDU Orderable Part List 30A, 3-wire power cables Add a circuit breaker on the PDU How to Add Circuit Breakers and Power CablesAdd a power cable to the PDU or RDP Customizing and Updating the PDU Testing the EPO wiring and switches How to Test the EPO SwitchSafety warnings Customizing and Updating the PDU ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit Upgrading the PDU monitor processor How to Download Firmware UpgradesDownloading firmware upgrades from a local computer Xmodem 80kW InfraStruXure PDU SpecificationsPD80F6FK1-M PD80G6FK1-M PD80L6FK1-M PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M Page Product Information InfraStruXure Standard WarrantyProduct Information Life-Support Policy APC Three-Phase SystemsHow to contact APC How to Obtain ServiceChanges in This Manual AppendixGeneral Changes Changes by page numberPage Index 80kW InfraStruXure PDU-Operation and Configuration UPS Page Page Page Page APC Worldwide Customer Support