Overview
User connection plate
For a description and location of the user connection plate, see () on page 8. For clarity, the user connection plate is shown in the following illustration in greater detail.
\
!
USER
©2001 MADE USA
1 | 2 | 3 | 4 |
| Contact Inputs |
|
Contact Outputs
!
ATS0 ATS1 ATS2 ATSEN | – + | Contact |
AC/DC | ||
| EPO 24V | EPO |
!
Connect the InfraStruXure PDU to the network of the InfraStruXure Manager through the ethernet port.
The user connection plate has four input contact connections for monitoring Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20 and page 64 for more information.
The user connection plate has four relay output connections for connection of Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20 and page 64 for more information.
Connect an Emergency Power Off (EPO) switch at one of three choices of EPO connections (24VDC, 24VAC, or contact closure). See page 60 for more information.
80kW InfraStruXure | 11 |