American Power Conversion PD80KL6FK1-M, PD80KG6FK1-M, PD80KF6FK1-M manual PDU Alarms

Page 32

PDU Display Interface

PDU Alarms

This table lists all alarms that can be generated by the InfraStruXure PDU, as displayed by the All Possible Alarms option, with numeric variables between the < > characters. Logged alarms will display specific numbers instead.

Alarm Condition

Explanation

Message When

Condition Cleared.

 

 

 

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated has dropped

Input Voltage V <Ln-N>

Voltage Under Limit

below the configured lower limit.

Back In Range

 

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated exceeded the

 

Voltage Over Limit

configured upper limit.

 

 

 

 

Output V <Ln-N> =<Value>

Phase-to-neutral output voltage for phase <L-N>

Output Voltage V <L-N>

Voltage Under Limit

dropped below the configured limit.

Back In Range

 

 

 

Output V <Ln-N>=<Value>

Phase-to-neutral output voltage for phase <L-N>

 

Voltage Over Limit

exceeded the configured limit.

 

 

 

 

Output I L<n>=<Value>

Current of output phase <n> exceeded the

Output Phase <N>

Current Over Limit

configured limit.

Current Within Limit

 

 

 

Output I L<n>=<Value>

Current of output phase <n> dropped below the

 

Current Under Limit

configured limit.

 

 

 

 

Output Neut=<Value>

Current on the neutral wire for the output phases

Output Neutral

Current Over Limit

exceeded the configured limit.

Current Within Limit

 

 

 

Output FDev=<Value>

Frequency of the output current is above or below

Output Frequency

Freq Out of Range

the range that is configured as acceptable.

Back In Range

 

 

 

Input Transformer

The temperature of the PDU transformer

Input Transformer

Temperature Too High

exceeded the normal limit, if applicable.

Temp. Back to Normal

 

 

 

Main Breaker Open

The Main input switch is Off.

Main Circuit Breaker

Alarm Active

 

Has Been Closed

 

 

 

<User Contact Name>

A user-configured contact connected to the PDU

Alarm Cleared

Alarm Active

monitoring unit is reporting an alarm condition.

 

 

 

 

No UPS Input

The Q1 circuit breaker is open, and the PDU is

None

Breaker Q1 Open

not receiving power from the UPS.

 

 

 

 

No Panel Feed

The Q2 & Q3 circuit breakers are open, and the

None

Breakers Q2&Q3 Open

PDU is not supporting connected equipment.

 

 

 

 

Atypical Bypass Mode

The system state as set by the Q1, Q2, & Q3

None

Alarm Active

breakers is in a bypass mode.

 

 

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit

Branch Ckt Pos: <nn>

Current Over Limit

breaker nn exceeded the configured limit.

Current Within Limit

 

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit

 

Current Under Limit

breaker nn dropped below the configured limit.

 

 

 

 

Fan Rotation Failure

There is a failure in one of the fans. The fan needs

None

Alarm <Active

to be replaced.

 

 

 

 

24

80kW InfraStruXure PDU—Operation and Configuration

Image 32
Contents 80kW InfraStruXure PDU Page How to find updates to this manual About This ManualAudience Companion manualsPage Contents System Operation Specifications Product Information Safety Safety symbols used in this manualCross-reference symbols used in this manual OverviewInstallation/Maintenance Maintenance performed while the PDU is receiving input powerTotal Power Off Emergency Power Off EPOEMI Overview InfraStruXure PDU ComponentsPDU front view exterior Front view interior  Wraparound Maintenance bypass Panel- Front view door openRear view interior PDU monitoring unit User connection plate  Page PDU Display Interface       Navigating through screens Top-level status screensTop-level menu screen Password-protected screens Power Factor Load-Meter ScreenVolt-Meter Screen Contacts Screen OverviewInput Contacts Open or ClosedPDU Display Interface How to connect contacts to the PDU monitoring unit Breakers Screen Main InputBypass Input Cross TieAlarms Screen New Logged ItemsEntire Log Clear LogAlarm Setup Alarm BeeperLoading Limits Voltage LimitsPDU Alarms Alarm Condition Explanation Message When Condition ClearedBranch Ckt Limits Panel ScreenBranch Ckt Loading Panel Configuration Distribution panelGlobal Panel Config Config Screen System PasswordSystem/Network Date/TimeOutput Config Electrical ConfigInput Config Factory Defaults Firmware UpdatesManufacturer Data System IDHow to Transfer the UPS into Maintenance Bypass Operation System OperationSystem Operation System Operation How to Return from Maintenance Bypass Operation Confirm Yes, UPS Load on No, Abort Confirm Yes, UPS into Bypass No, Abort How to Ensure Total Power Off Set the UPS System Enable switch to the OFF positionSystem Operation How to Apply Power to the System PowerView RM Rev 000 English Please wait Top-Level Status Screen System Operation Communication Configuration InfraStruXure PDU Management OptionsInfraStruXure Manager Network management interfacesConfiguring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure ManagerConnect the InfraStruXure PDU to your network Configuring the Network Management InterfaceConfiguration Overview TCP/IP configuration methods Device IP Configuration WizardBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where Remote access to the control console Local access to the control consoleUse apc for the User Name and Password Choose Network from the Control Console menu Use apc for both User Name and PasswordControl console Web interface Snmp FTP and SCP 80kW InfraStruXure PDU-Operation and Configuration Important Safety Instructions Customizing and Updating the PDUCircuit Breakers Power CablesPDU Orderable Part List 30A, 3-wire power cables Add a circuit breaker on the PDU How to Add Circuit Breakers and Power CablesAdd a power cable to the PDU or RDP Customizing and Updating the PDU How to Test the EPO Switch Testing the EPO wiring and switchesSafety warnings Customizing and Updating the PDU ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit Upgrading the PDU monitor processor How to Download Firmware UpgradesDownloading firmware upgrades from a local computer Xmodem Specifications 80kW InfraStruXure PDUPD80F6FK1-M PD80G6FK1-M PD80L6FK1-M PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M Page InfraStruXure Standard Warranty Product InformationProduct Information APC Three-Phase Systems Life-Support PolicyHow to Obtain Service How to contact APCAppendix Changes in This ManualGeneral Changes Changes by page numberPage Index 80kW InfraStruXure PDU-Operation and Configuration UPS Page Page Page Page APC Worldwide Customer Support