American Power Conversion SYMSTRF3I Electrical Requirements EPO Switch, EPO Specifications

Page 19

Electrical Requirements - EPO Switch

The SymmetraTM Power Array can be connected to either a dry contact or 24Vdc Emergency Power Off switch. The terminal connections for the EPO switch are physically isolated from the primary circuitry of the Power Array system.

EPO Specifications

The EPO circuit is considered a Class 2 and SELV circuit.

SELV is an acronym for “Safety Extra Low Voltage.” SELV is a common term in Europe and IEC standards. A SELV circuit is isolated from primary circuitry through an isolating transformer and designed so that under normal conditions, the voltage is limited to 42.4 Vpeak or 60 Vdc.

A Class 2 Circuit is a common term in North America and in UL and CSA standards. It is defined in the Canadian Electrical Code (C22.1, Section 16) and in the National Electrical Code (NFPA 70, Article 725). SELV and Class 2 circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is SELV or Class 2. If there is a question, use a contact closure switch. Use one of the following cable types to connect the SymmetraTM to the REPO switch:

CL2 - Class 2 cable for general purpose use.

CL2P - Plenum cable for use in ducts, plenums, and other space used for environmental air. CL2R - Riser cable for use in a vertical run in a shaft or from floor to floor.

CL2X - Limited Use cable for use in dwellings and for use in raceway.

For installation in Canada, the cable should be CSA Certified, type ELC (Extra-Low-Voltage Control Cable).

990-7164-001

Site Requirements - Page 5

 

Image 19
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Life Support Policy Limited WarrantyTable of Contents Page Safety Symbols Safety InformationRadio Frequency Interference Operation SymbolsModels WelcomeFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SYMSTRF3I SymmetraTM Components Description Specific To ModelBasic Operation Glossary of SymmetraTM Terms 8 Introduction Front Clearance Site RequirementsOperating Space Requirements Rear ClearanceModels Structural RequirementsEnvironmental Requirements Short-Term Battery Module Storage RequirementsHeat Output VAC Electrical Requirements Input/OutputEPO Specifications Electrical Requirements EPO SwitchElectrical Wiring Overview Inspect Packaging SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Receiving the SymmetraTMMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Model SYMSTRF3I Electrical InstallationElectrical Requirements EPO Switch Wiring RequiredElectrical Wiring Overview Input/Output Wiring Wire Size Input/Output Wiring ProcedureMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Wiring Symbol Description Minimum Wire Gauge Bypass Balance Transformer Wiring Procedure OptionalWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Securing The Frame Setting The Leveling Feet Startup ProcedurePower Module Installation Battery Module Installation System Startup Procedure System Settings Setup Configuration and Advanced OperationConfiguration Display SettingsAdvanced Operation PowerView Interface PowerView Component Description PowerView ComponentsLanguage Chip Replacement Procedure Language ConfigurationTop-Level Menu Screen Startup ScreenStatus ControlSetup PowerView CommandsLogging AccessoriesFunction Options DisplayHelp DiagnosticsWall Mounting the PowerView PowerView Meaning Corrective Action Message Start-Up TroubleshootingPowerView Meaning Corrective Action Message General Threshold PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassGeneral PowerView Meaning Corrective Action Message6 Troubleshooting Appendix B Module Failure Alarm Indicators Module ReplacementReturning Modules to APC Technical Support & Obtaining Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementReplacement Module Verification Power Module ReplacementReplacement RIM Verification Main Intelligence Module ReplacementReplacement MIM Verification Redundant Intelligence Module Replacement6 Module Replacement Appendix C Input Specifications SpecificationsOperation Physical Specifications Output SpecificationsCompliance Specifications Page Tel0800 180