American Power Conversion SYMSTRF3I user manual Site Requirements, Operating Space Requirements

Page 15

Site Requirements

Operating Space Requirements

The SymmetraTM is 23.5” (60cm) wide, and 27.5” (70cm) deep. No space is required on the sides of the SymmetraTM frame.

Rear Clearance

νA minimum of 12" (30 cm) of clearance is required behind the frame for adequate airflow.

νThe system enable switch must remain accessible.

νThe back of the SymmetraTM must be accessible for the electrician to install wiring.

Front Clearance

νA minimum of 48" (122 cm) of clearance is required in front of the frame.

νThe PowerView interface must remain accessible.

νThe front of the SymmetraTM must be accessible to install and replace power and battery modules.

Notice!

νThe voltage transformer in the SYMINIF and SYMSTRF models emits an electro magnetic field (EMF) that can interfere with the normal function of a computer monitor. Do not install these models in close proximity to a computer monitor. The EMF is not of sufficient magnitude to cause interference with other equipment.

990-7164-001

Site Requirements - Page 1

 

Image 15
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Life Support Policy Limited WarrantyTable of Contents Page Safety Symbols Safety InformationRadio Frequency Interference Operation SymbolsWelcome ModelsFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SYMSTRF3I SymmetraTM Components Description Specific To ModelBasic Operation Glossary of SymmetraTM Terms 8 Introduction Front Clearance Site RequirementsOperating Space Requirements Rear ClearanceModels Structural RequirementsShort-Term Battery Module Storage Requirements Environmental RequirementsHeat Output VAC Electrical Requirements Input/OutputEPO Specifications Electrical Requirements EPO SwitchElectrical Wiring Overview Inspect Packaging SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Receiving the SymmetraTMMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Model SYMSTRF3I Electrical InstallationElectrical Requirements EPO Switch Wiring RequiredElectrical Wiring Overview Input/Output Wiring Input/Output Wiring Procedure Wire SizeMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Wiring Symbol Description Minimum Wire Gauge Bypass Balance Transformer Wiring Procedure OptionalWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Securing The Frame Setting The Leveling Feet Startup ProcedurePower Module Installation Battery Module Installation System Startup Procedure System Settings Setup Configuration and Advanced OperationConfiguration Display SettingsAdvanced Operation PowerView Interface PowerView Component Description PowerView ComponentsLanguage Chip Replacement Procedure Language ConfigurationTop-Level Menu Screen Startup ScreenStatus ControlSetup PowerView CommandsLogging AccessoriesFunction Options DisplayHelp DiagnosticsWall Mounting the PowerView PowerView Meaning Corrective Action Message Start-Up TroubleshootingPowerView Meaning Corrective Action Message General Threshold PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassGeneral PowerView Meaning Corrective Action Message6 Troubleshooting Appendix B Module Failure Alarm Indicators Module ReplacementReturning Modules to APC Technical Support & Obtaining Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementReplacement Module Verification Power Module ReplacementReplacement RIM Verification Main Intelligence Module ReplacementReplacement MIM Verification Redundant Intelligence Module Replacement6 Module Replacement Appendix C Specifications Input SpecificationsOperation Output Specifications Physical SpecificationsCompliance Specifications Page Tel0800 180