Site Requirements
Operating Space Requirements
The SymmetraTM is 23.5” (60cm) wide, and 27.5” (70cm) deep. No space is required on the sides of the SymmetraTM frame.
Rear Clearance
νA minimum of 12" (30 cm) of clearance is required behind the frame for adequate airflow.
νThe system enable switch must remain accessible.
νThe back of the SymmetraTM must be accessible for the electrician to install wiring.
Front Clearance
νA minimum of 48" (122 cm) of clearance is required in front of the frame.
νThe PowerView interface must remain accessible.
νThe front of the SymmetraTM must be accessible to install and replace power and battery modules.
Notice!
νThe voltage transformer in the SYMINIF and SYMSTRF models emits an electro magnetic field (EMF) that can interfere with the normal function of a computer monitor. Do not install these models in close proximity to a computer monitor. The EMF is not of sufficient magnitude to cause interference with other equipment.