American Power Conversion SYMSTRF3I user manual Wiring Verification Procedure

Page 34

Wiring Verification Procedure

The following procedure will ensure that the SymmetraTM has been wired properly. The electrician who per- formed this electrical installation should complete this checklist and deliver it to the system operator.

Caution!

νEnsure all switches (system enable, maintenance bypass , input circuit breaker, and bypass circuit breaker) are in the “off ” or “stand by” position. Ensure all load equipment is turned off or is unplugged from the Power Array.

Note: If a bypass transformer was installed, disregard the bypass circuit breaker.

θ1. Apply power to the system input, and measure voltage at the input terminal block. Record measured voltages below:

L1-Neutral:

______________________

L2-Neutral:

______________________

L3-Neutral:

______________________

Caution!

νMeasured voltage must be between 184V and 265V. If it is not, STOP! Verify correct wiring from the power source to the input wiring connections. Repeat step 1.

θ2. Connect the PowerView display as shown below:

θ3. Switch the input circuit breaker and bypass breaker on, then switch the system enable switch on.

Note: The system will make some clicking sounds as it powers up, and may display fault messages on the PowerView display. Disregard these messages at this time.

Page 10 - Electrical Installation

990-7166-001

 

Image 34
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Limited Warranty Life Support PolicyTable of Contents Page Safety Information Safety SymbolsOperation Symbols Radio Frequency InterferenceModels WelcomeFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SymmetraTM Components Description Specific To Model SYMSTRF3IBasic Operation Glossary of SymmetraTM Terms 8 Introduction Rear Clearance Site RequirementsOperating Space Requirements Front ClearanceStructural Requirements ModelsEnvironmental Requirements Short-Term Battery Module Storage RequirementsHeat Output Electrical Requirements Input/Output VACElectrical Requirements EPO Switch EPO SpecificationsElectrical Wiring Overview Receiving the SymmetraTM SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Inspect PackagingMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Electrical Installation Model SYMSTRF3IEPO Switch Wiring Required Electrical RequirementsElectrical Wiring Overview Input/Output Wiring Wire Size Input/Output Wiring ProcedureMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Bypass Balance Transformer Wiring Procedure Optional Wiring Symbol Description Minimum Wire GaugeWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Startup Procedure Securing The Frame Setting The Leveling FeetPower Module Installation Battery Module Installation System Startup Procedure Display Settings Configuration and Advanced OperationConfiguration System Settings SetupAdvanced Operation PowerView Interface PowerView Components PowerView Component DescriptionLanguage Configuration Language Chip Replacement ProcedureStartup Screen Top-Level Menu ScreenControl StatusPowerView Commands SetupAccessories LoggingDisplay Function OptionsDiagnostics HelpWall Mounting the PowerView Troubleshooting PowerView Meaning Corrective Action Message Start-UpPowerView Meaning Corrective Action Message General Failure PowerView Meaning Corrective Action Message ModuleAlarm ThresholdPowerView Meaning Corrective Action Message Bypass FaultPowerView Meaning Corrective Action Message General6 Troubleshooting Appendix B Module Replacement Module Failure Alarm IndicatorsTechnical Support & Obtaining Replacement Module Returning Modules to APCBattery Module Replacement Replacement Battery Module VerificationPower Module Replacement Replacement Module VerificationRedundant Intelligence Module Replacement Main Intelligence Module ReplacementReplacement MIM Verification Replacement RIM Verification6 Module Replacement Appendix C Input Specifications SpecificationsOperation Physical Specifications Output SpecificationsCompliance Specifications Page Tel0800 180