American Power Conversion SYMSTRF3I user manual Output Specifications, Physical Specifications

Page 66

Output Specifications

Nominal Output Voltage

220 / 230 / 240 VAC, 50/60 Hz, 1 phase, 3 wire

 

 

Output Power kVA (kW)

4-16 kVA (2.8 to 11.2 kW)

 

 

Load Power Factor

0 - 1

 

 

Output Frequency

50/60 Hz +/- 0. 1% Free Running

 

50/60 Hz +/- 3 Hz Sync to Bypass; User Settable

 

 

Output Voltage Regulation

<+/- 3% for No-load to Full-load, Min AC input to Max AC, Min DC to Max DC,

Steady State

Linear or Non-linear load or any combination

 

 

Output Voltage Regulation

<+/- 5% for 100% load application or removal Linear or Non-linear load

Transient/Dynamic

 

 

 

Recovery Time

< 10 milliSec i.e. Half Cycle to Steady state

 

 

Total Harmonic Distortion

< 2% for Linear Loads

 

< 5% for 100% non-linear loads

 

 

Load Crest Factor Supported

5:1

 

 

Overload Capacity

150% for 30 Secs, 125% for 10 mins

 

 

Efficiency

> 90% @ Full Load - Linear or Non-linear loads

 

 

Physical Specifications

Audible Noise - Fully Loaded

62dBA

 

 

Dimensions

Width: 60cm Depth: 70cm Height: 122 cm

 

 

Weight - Fully Loaded

298Kgs

 

 

Heat Dissipation - Max with

13,456 BTU's

Batteries Charging

 

 

 

Compliance Specifications

VDE-GS Verifications

EN 60950, EN 50091, IEC 950, VDE 0805

Page 2 - Specifications - Appendix D

990-7172-001

 

Image 66
Contents 380V/400V/415V 31 Frame Model SYMSTRF3I Limited Warranty Life Support PolicyTable of Contents Page Safety Information Safety SymbolsOperation Symbols Radio Frequency InterferenceWelcome ModelsFrame Model Description Illustration System Components SymmetraTM Component Description Model Specific Details SYMSTRF3I SymmetraTM Components Description Specific To Model SYMSTRF3IBasic Operation Glossary of SymmetraTM Terms 8 Introduction Rear Clearance Site RequirementsOperating Space Requirements Front ClearanceStructural Requirements ModelsShort-Term Battery Module Storage Requirements Environmental RequirementsHeat Output Electrical Requirements Input/Output VACElectrical Requirements EPO Switch EPO SpecificationsElectrical Wiring Overview Receiving the SymmetraTM SymmetraTM Component Shipping Weight Shipping DimensionsReceiving and Unpacking Inspect PackagingMoving The SymmetraTM Frame and Modules Unpacking the SymmetraTM Frame 4 Receiving and Unpacking Electrical Installation Model SYMSTRF3IEPO Switch Wiring Required Electrical RequirementsElectrical Wiring Overview Input/Output Wiring Input/Output Wiring Procedure Wire SizeMinimum Emergency Power Off Switch Wiring Required Emergency Power Off Switch Wiring Procedure Bypass Balancing Transformer Wiring Optional Bypass Balance Transformer Wiring Procedure Optional Wiring Symbol Description Minimum Wire GaugeWiring Verification Procedure Reported Output Voltage OutVHz APC Worldwide Technical Support Telephone Numbers Startup Procedure Securing The Frame Setting The Leveling FeetPower Module Installation Battery Module Installation System Startup Procedure Display Settings Configuration and Advanced OperationConfiguration System Settings SetupAdvanced Operation PowerView Interface PowerView Components PowerView Component DescriptionLanguage Configuration Language Chip Replacement ProcedureStartup Screen Top-Level Menu ScreenControl StatusPowerView Commands SetupAccessories LoggingDisplay Function OptionsDiagnostics HelpWall Mounting the PowerView Troubleshooting PowerView Meaning Corrective Action Message Start-UpPowerView Meaning Corrective Action Message General Failure PowerView Meaning Corrective Action Message ModuleAlarm ThresholdPowerView Meaning Corrective Action Message Bypass FaultPowerView Meaning Corrective Action Message General6 Troubleshooting Appendix B Module Replacement Module Failure Alarm IndicatorsTechnical Support & Obtaining Replacement Module Returning Modules to APCBattery Module Replacement Replacement Battery Module VerificationPower Module Replacement Replacement Module VerificationRedundant Intelligence Module Replacement Main Intelligence Module ReplacementReplacement MIM Verification Replacement RIM Verification6 Module Replacement Appendix C Specifications Input SpecificationsOperation Output Specifications Physical SpecificationsCompliance Specifications Page Tel0800 180